Advanced functions
127
A
dv
an
ce
d
Fu
nc
tio
ns
8.21 Operating sound select (Carrier frequency
change)
Group
Code
Parameter Name
Setting
Range
Default
Unit
Function
group 2
H39
[Carrier frequency]
-
1 - 15
3
kHz
This parameter affects the sound of the inverter during operation.
H39 When setting carrier frequency high,
Motor sound reduced
Inverter heat loss increased
Inverter noise increased
Inverter leakage current increased
8.22 2
nd
motor operation
Group
Code
Parameter Name
Setting
Range
Default
Unit
Function
group 2
H81
[2nd motor accel time]
-
0 - 6000 5.0
sec
H82
[2nd motor decel time]
-
0 - 6000 10.0
sec
H83
[2nd motor base freq.]
-
30 - 400 50.00
Hz
H84
[2nd motor V/F pattern]
-
0 - 2
0
H85
[2nd motor Positive torque boost]
-
0 - 15
5
%
H86
[2nd motor Negative torque boost] -
0 - 15
5
%
H87
[2nd motor stall prevention level]
-
30 - 150 130
%
H88
[2nd motor electronic thermal level
for 1 min]
-
50 - 200 120
%
H89
[2nd motor electronic thermal level
for continuous operation]
-
50 - 150 100
%
H90
[2nd motor rated current]
-
0.1-100
26.3
A
I/O group
I17
[Multi-function Input terminal
P1Function select]
-
0 - 30
0
-
-
I20
[Multi-function Input terminal
P4Function select]
12
3
Set the terminal among Multi-function input P1 thru P4for second motor operation.
To define the terminal P4 as second motor operation, set I20 to 12.
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...
Page 224: ...210 ...