47
Function list
Fu
nc
tio
ns
Lis
t
Function group 2
LED
display
Address
for
communi-
cation
Parameter
name
Min/
Max
range
Description
Factory
defaults
Adj.
during
run
Page
H17
A311
[S-Curve
accel/decel
start side]
1-100
[%]
Set the speed reference value to form a
curve at the start during accel/decel. If it is
set higher, linear zone gets smaller.
40
X
H18
A312
[S-Curve
accel/decel
end side]
1-100
[%]
Set the speed reference value to form a
curve at the end during accel/decel. If it is
set higher, linear zone gets smaller.
40
X
H19
A313
[Input/output
phase loss
protection
select]
0 - 3
0 Disabled
1
Output phase
protection
0
O
2
Input
phase
protection
3
Input/output phase
protection
H21
A315
[Restart after
fault reset
selection]
0 -1
This parameter is activated when drv is
set to 1 or 2 (Run/Stop via Control
terminal).
Motor accelerates after the fault condition
is reset while the FX or RX terminal is
ON.
0
O
H22
1)
A316
[Speed Search
Select]
0 - 15
This parameter is active to prevent any
possible fault when the inverter outputs
its voltage to the running motor.
0
X
1.
H20-
[Power
On
start]
2.
Restart
after
instant
power
failure
3.
Operation
after fault
4.
Normal
accel
Bit 3
Bit 2
Bit 1
Bit 0
0 -
-
-
-
1 -
-
-
2 -
-
-
3 -
-
4 -
-
-
1)
Normal acceleration has first priority. Even though #4 is selected along with other bits, Inverter
performs Speed search #4.
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...
Page 224: ...210 ...