Function list
Function group 1
LED
display
Address
for
communi-
cation
Parameter
name
Min/
Max
range
Description
Factory
defaults
Adj.
during
run
Page
F59
A23B
[Stall
prevention
select]
0 - 7
This parameter stops accelerating during
acceleration, decelerating during constant
speed run and stops decelerating during
deceleration.
4
X
During
Decel
During
constant run
During
Accel
Bit 2
Bit 1
Bit 0
0 -
-
-
1 -
-
2 -
-
3 -
4
-
-
5
-
6
-
7
F60
A23C
[Stall
prevention
level]
30 -
200
[%]
This parameter sets the amount of current
to activate stall prevention function during
Accel, constant or Decel run.
The set value is the percentage of the
H33- [Motor rated current].
130
X
F63
A23F
[Save
up/down
frequency
select]
0 - 1
This parameter decides whether to save
the specified frequency during up/down
operation.
When 1 is selected, the up/down
frequency is saved in F64.
0
X
F64
2)
A240
[Save
up/down
frequency]
If ‘Save up/down frequency’ is selected at
F63, this parameter saves the frequency
before the inverter stops or decelerated.
0.00
X
F65
A241
[Up-down
mode select]
0-2
We can select up-down mode among
three thing
0
X
0
Increases goal frequency as a
standard of Max. frequency/Min.
frequency
1
Increases as many as step frequency
according to edge input
2 Available to combine 1 and 2
1)
It is indicated when setting bit 2 of F59 as 1
2)
Set F63 to 1 to display this parameter.
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...
Page 224: ...210 ...