52
Function list
Function group 2
LED
display
Address
for
communi-
cation
Parameter
name
Min/
Max
range
Description
Factory
defaults
Adj.
during
run
Page
H70
A346
[Frequency
Reference for
Accel/Decel]
0 - 1
0
Based on Max freq (F21)
0
X
1
Based on Delta freq.
H71
A347
[Accel/Decel
time scale]
0 - 2
0
Settable unit: 0.01 second.
1
O
1
Settable unit: 0.1 second.
2
Settable unit: 1 second.
H72
A348
[Power on
display]
0 - 17
This parameter selects the parameter to
be displayed on the keypad when the
input power is first applied.
0
O
0
Frequency command
1
Accel time
2
Decel time
3
Drive mode
4
Frequency mode
5
Multi-Step frequency 1
6
Multi-Step frequency 2
7
Multi-Step frequency 3
8
Output current
9
Motor rpm
10 Inverter DC link voltage
11 User display select (H73)
12 Fault display
13 Direction of motor rotation select
14 Output current 2
15 Motor rpm 2
16 Inverter DC link voltage 2
17 User display select 2
H73
A349
[Monitoring
item select]
0 - 2
One of the following can be monitored via
vOL - [User display select].
0
O
0
Output voltage [V]
1
Output power [kW]
2
Torque [kgf
m]
H74
A34A
[Gain for Motor
rpm display]
1 -
1000
[%]
This parameter is used to change the
motor rotating speed (r/min) to
mechanical speed (m/mi) and display it.
100
O
H75
A34B
[DB resistor
operating rate
limit select]
0 - 1
0
Unlimited
1
O
1
Use DB resistor for the H76 set time.
H76
A34C
[DB resistor
operating rate]
0 -
30[%]
Set the percent of DB resistor operating
rate to be activated during one sequence
of operation.
10
O
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...
Page 224: ...210 ...