RS485 communication
177
Com
mu
nica
tion
11.5 Communication protocol (MODBUS-RTU)
Use Modbus-RTU protocol (Open protocol).
Computer or other hosts can be Master and inverters Slave. Inverter responds to
Read/Write command from Master.
Code
Description
Function
Code
0x03
Read Hold Register
0x04
Read Input Register
0x06
Preset Single Register
0x10
Preset Multiple Register
Exception
Code
0x01
ILLEGAL FUNCTION
0x02
ILLEGAL DATA ADDRESS
0x03
ILLEGAL DATA VALUE
0x06
SLAVE DEVICE BUSY
User define 0x14
1.Write Disable (Address 0x0004 value is 0).
2.Read Only or Not Program during Running.
11.6 Communication protocol (LS BUS)
Basic format
Command message (Request):
Command message
(Request):
ENQ
Drive No.
CMD
Data
SUM
EOT
1 byte
2 bytes
1 byte
n bytes
2 bytes
1 byte
Normal response
(Acknowledge
Response)
ACK
Drive No.
CMD
Data
SUM
EOT
1 byte
2 bytes
1 byte
n * 4 bytes
2 bytes
1 byte
Negative response
(Negative Acknowledge
Response)
NAK
Drive No.
CMD
Error code
SUM
EOT
1 byte
2 bytes
1 byte
2 bytes
2 bytes
1 byte
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...
Page 224: ...210 ...