81
Basic Functions
B
as
ic
Fu
nc
tio
ns
Rotating direction select via
–10 - +10[V] input of V1
7.3.5
terminal
Group
Code
Parameter Name
Setting
Range
Default
Unit
Drive group
frq
[Frequency setting]
2
0 - 8
0
drv
[Drive mode]
-
0 - 4
1
Set
frq
to 2.
Inverter is operating as the table below regardless of Drive mode setting.
FWD RUN Command
REV RUN Command
0 - +10 [V]
FWD RUN
REV RUN
-10 - 0 [V]
REV RUN
FWD RUN
►
Motor runs in Forward direction when input voltage to V1-CM is 0-10[V] and FWD RUN
command is active. When input voltage polarity is reversed to
–10-0[V] during FWD
RUN, motor decelerates to stop and runs in reverse direction.
►
When input voltage to V1-CM is 0-10[V] and REV RUN command is active, motor runs
in Reverse direction and if -10-0[V] is input, motor rotating direction is reverse.
FX/RX Run Disable
7.3.6
Group
Code
Parameter Name
Setting
Range
Default
Unit
Drive group
drC
[Direction of motor rotation
select]
-
F, r
F
Function
group 1
F 1
[Forward/Reverse run
disable]
-
0 - 2
0
Select the direction of motor rotation.
0: Forward and Reverse run enable
1: Forward run disable
2: Reverse run disable
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...
Page 224: ...210 ...