Advanced functions
122
8.18 Energy-saving operation
Group
Code
Parameter Name
Setting
Range
Default
Unit
Function
group 1
F40
[Energy-saving operation] -
0 - 30
0
%
Set the amount of output voltage to be reduced in F40.
Set as the percent of Max output voltage.
For fan or pump applications, energy consumption can be dramatically reduced by
decreasing the output voltage when light or no load is connected.
8.19 Speed search
Group
Code
Parameter Name
Setting
Range
Default
Unit
Function
group 2
H22
[Speed search select]
-
0 - 15
0
H23
[Current level]
-
80 - 200
100
%
H24
[Speed search P gain]
-
0 - 9999
100
H25
[Speed search I gain]
-
200
I/O group
I54
[Multi-function relay1 select] 15
0 - 27
12
I55
[Multi-function relay2 select] 15
17
This is used to prevent possible fault from occurring if the inverter outputs the voltage
during operation after the load is removed.
The inverter estimates the motor rpm based on output current. Therefore, detecting
exact speed is difficult.