Monitoring
141
M
on
ito
rin
g
9 Monitoring
9.1 Operating status monitoring
Output cu
r
rent
9.1.1
Group
Code
Parameter Name
Setting Range Default
Unit
Drive group
CUr
[Output current]
-
Inverter output current can be monitored in Cur.
Motor RPM
9.1.2
Group
Code
Parameter Name
Setting
Range
Default
Unit
Drive group
rPM
[Motor RPM]
-
Function
group 2
H31
[Number of motor poles]
-
2 - 12
4
H49
[PID control select]
-
0 - 1
0
H74
[Gain for Motor rpm
display]
-
1 - 1000
100
%
Motor rpm can be monitored in rPM.
►
When H40 is set to 0 {V/F control} or 1 {PID control}, the Inverter output frequency (f) is
displayed in RPM using the formula below. Motor slip is not considered.
►
In case that H49 code is 1, Feed back amount is converted into frequency.
►
H31: Enter the number of rated motor poles on the nameplate.
►
H74: This parameter is used to change the motor speed display to rotating speed (r/min)
or mechanical speed (m/min).
100
74
31
120
H
H
f
RPM