
Advanced functions
95
A
dv
an
ce
d
Fu
nc
tio
ns
8 Advanced functions
8.1 DC brake
Stopping motor by DC brake
8.1.1
Group
Code
Parameter Name
Setting
Range
Default
Unit
Function
group 1
F 4
[Stop mode select]
1
0 - 3
0
F 8
[DC Brake start frequency] -
0.1 - 60
5.00
Hz
F 9
[DC Brake wait time]
-
0 - 60
0.1
sec
F10
[DC Brake voltage]
-
0 - 200
50
%
F11
[DC Brake time]
-
0 - 60
1.0
sec
Set F4 - [Stop mode select] to 1.
F 8: The frequency at which the DC brake will become active.
F 9: Inverter output will hold for this time after F8 - [DC Brake start frequency] before
applying F10 - [DC Brake voltage].
F10: Set this value as a percent of H33
– [Motor rated current].
F11: It sets the time for F10 - [DC Brake voltage] to be applied to the motor after F 9 -
[DC Brake wait time].
If excessive DC Brake voltage is set or DC Brake time is set too long, it may cause motor
overheating and damage to the motor.
►
Setting F10 or F11 to 0 will disable DC brake.
►
F 9
– [DC Brake Wait time]: When load inertia is large or F 8 – [DC Brake Start
Frequency] is high, over current trip may occur. It can be prevented using F9.
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...
Page 224: ...210 ...