Basic Functions
88
7.5 V/F control
Linear V/F pattern operation
7.5.1
Group
Code
Parameter Name
Setting
Range
Default Unit
Function group 1
F22 [Base frequency]
-
30 - 400 60.00 Hz
F23 [Start frequency]
-
0.1 - 10.0 0.50
Hz
F30 [V/F pattern]
0
0 - 4
0
Function group 2 H40 [Control mode select]
-
0 - 2
0
Set F30 to 0 {Linear}.
This pattern maintains a linear Volts/frequency ratio from F23 - [Start frequency] to F22-
[Base frequency]. This is appropriate for constant torque applications.
►
Base Frequency: Inverter outputs its rated voltage at this level. Enter the motor
nameplate frequency.
►
Start Frequency: Inverter starts to output its voltage at this level.
Square V/F pattern
7.5.2
Group
Code
Parameter Name
Setting
Range
Default Unit
Function group 1
F30 [V/F pattern]
1
0 - 4
0
Set F30 to 1{Square}.
This pattern maintains squared volts/hertz ratio. Appropriate applications are fans, pumps, etc.