Advanced functions
125
A
dv
an
ce
d
Fu
nc
tio
ns
8.20 Auto restart try
Group
Code
Parameter Name
Setting
Range
Default Unit
Function
group 2
H26
[Number of Auto Restart try]
-
0 - 10
0
H27
[Auto Restart time]
-
0 - 60
1.0
sec
This parameter sets the number of times auto restart is activated in H26.
It is used to prevent the system down caused by internal protection function activated
by the causes such as noise.
►
H26: Auto restart will become active after the H27. H26
– [Number of Auto restart try] is
reduced by 1 when it is active. If the trip outnumbers the preset restart try, auto restart
function is deactivated. If the setting is reset via the control terminal or the STOP/RST
key on the keypad, the number of auto restart try set by user is automatically entered.
►
If there is no more trip occurring for 30 sec after Auto restart operation, the H26 is
restored to the preset value.
►
When operation is stopped due to Low voltage {Lvt} or Emergency stop {EST}, Inverter
Overheat {Oht}, and Hardware Trip {HWt}, Auto restart will be deactivated.
►
After the H27- [Auto Restart time], the motor starts acceleration automatically via speed
search (H22-25).
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...
Page 224: ...210 ...