Monitoring
146
Fault History Monitoring
9.3.2
Group
Code
Parameter Name
Setting
Range
Default
Unit
Function
group 2
H 1
[Fault history 1]
-
-
-
H 5
[Fault history 5]
H 6
[Reset fault history]
-
0 - 1
0
H 1 - H 5: Up to 5 faults information is stored.
H 6: Previous fault information stored in the code H1 thru H5 is all cleared.
►
When a fault occurs during operation, it can be monitored in the
nOn
.
►
When the fault condition is reset via the STOP/RST key or multi-function terminal,
information displayed in the
nOn
will be moved to H1. In addition, the previous fault info
stored in H1 will be automatically moved to H2. Therefore, the updated fault info will be
stored in the H1.
►
When more than 1 fault occurred at the same time, up to 3 types of faults will be stored
in one code.
Fault types
Operating status at fault