Protective functions
164
10.4 Output phase loss protection
Group
Code
Parameter Name
Setting
Range
Default
Unit
Function
group 2
H19
[Input/Output phase loss
protection select]
1
0 - 3
0
Set H19 value to 1.
Output phase loss: Inverter output is shut off at the event of more than one phase loss
among U, V and W.
Input phase loss: Inverter output is blocked at the event of more than one phase loss
among R, S and T. If there is no input phase loss, output is shut off when it is time to
replace DC link capacitor.
Set H33 [Motor rated current] correctly. If the actual motor rated current and the value of H33
are different, output phase loss protection function could not be activated.
H19
[Input/Output phase
loss protection
select]
0 Not used
1 Output phase loss protection
2 Input phase loss protection
3 Input/output phase loss protection
10.5 External trip signal
Group
Code
Parameter Name
Setting
Range
Default
Unit
I/O group
I17
[Multi-function input terminal P1
define]
0 - 30
0
-
-
I19
[Multi-function input terminal
P3 define]
18
2
I20
[Multi-function input terminal
P4 define]
19
3
Select a terminal among P1 thru P4 to output external trip signal.
Set I19 and I20 to 18 and 19 to define P3 and P4 as External A contact and B contact
►
External trip signal input A contact (N.O.): Normal open contact input. When a P3
terminal set to
“Ext trip-A” is ON (Closed), inverter displays the fault and turns off its
output.
►
External trip signal input B contact (N.C.): Normal close contact input. When a P4
terminal set to
“Ext trip-B” is OFF (Open), inverter displays the fault and turns off its
output.
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...
Page 224: ...210 ...