42
Function list
Function group 1
LED
display
Address
for
communi-
cation
Parameter
name
Min/
Max
range
Description
Factory
defaults
Adj.
during
run
Page
F30
A21E
[V/F pattern]
0 - 4
0 Linear
0
X
1 Square
2 User V/F
3 High Torque 1
4 High Torque 2
F31
1)
A21F
[User V/F
frequency 1]
0 -
400
[Hz]
It is used only when V/F pattern is set to
2(User V/F)
It cannot be set above F21
– [Max
frequency].
The value of voltage is set in percent of
H70
– [Motor rated voltage].
The values of the lower-numbered
parameters cannot be set above those of
higher-numbered.
12.50
X
F32
A220
[User V/F
voltage 1]
0 -
100
[%]
25
X
F33
A221
[User V/F
frequency 2]
0 -
400
[Hz]
25.00
X
F34
A222
[User V/F
voltage 2]
0 -
100
[%]
50
X
F35
A223
[User V/F
frequency 3]
0 -
400
[Hz]
37.50
X
F36
A224
[User V/F
voltage 3]
0 -
100
[%]
75
X
F37
A225
[User V/F
frequency 4]
0 -
400
[Hz]
50.00
X
F38
A226
[User V/F
voltage 4]
0 -
100
[%]
100
X
F39
A227
[Output
voltage
adjustment]
40 -
110
[%]
This parameter adjusts the amount of
output voltage.
The set value is the percentage of input
voltage.
100
X
F40
A228
[Energy-
saving level]
0 - 30
[%]
This parameter decreases output voltage
according to load status.
0
0
F50
A232
[Electronic
thermal select]
0 - 1
This parameter is activated when the
motor is overheated (time-inverse).
0
0
1)
Set F30 to 2(User V/F) to display this parameter.
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...
Page 224: ...210 ...