64
Function list
Application Group
LED
display
Address
for
communi-
cation
Parameter
name
Min/
Max
range
Description
Factory
defaults
Adj.
during
run
Page
A18
2)
A512
[Aux Stop
Delay Time]
0.1-
600.0
[s]
The auxiliary motors turns on or off after
the auxiliary motor stop delay time
elapses.
5.0
O
A19
2)
A513
[PID Acc Time]
0-
600.0
[s]
When the auxiliary motor stops, the main
motor accelerates up to the auxiliary motor
restart frequency set at A13, 14 (Start Freq
1, 2) based on the acceleration time set at
A20 (PID Acc Time).
5.0
O
A20
2)
A514
[PID Dec
Time]
0-
600.0
[s]
When an auxiliary motor starts, the main
motor decelerates to the auxiliary motor
deceleration frequency set at A15, 16 (Stop
Freq 1, 2) based on the deceleration time
set at A19 (PID Dec Time).
5.0
O
A21
2)
A515
[Aux All Stop]
0-1
0
No
No
O
1
Enable Aux All Stop
A22
2)
A516
[Aux On/Off
Sequence]
0-1
Sets the operating priority of MMC.
0
O
0
First In First Out
1
First In Last Out
A23
2)
A517
[Auto Change
Select]
0-1
0
No
No
O
1
Enable Aux Auto Change
A24
3)
A518
[Auto Change
Time]
1-
6000
[m]
Sets the auto change intervals.
6
X
A25
3)
A519
[Auto Change
Level]
startFr
eq-
400
[Hz]
All the conditions for Auto Change are met
under the frequency in which output
frequency of Main motors are set in A25.
A25 is the frequency to activate Auto
Change.
20.00
O
A26
3)
A51A
[Start Motor]
1-2
Sets the start auxiliary motor.
1
X
A27
3)
A51B
[Auto Change
Operation
Time]
0-
6000
[m]
Indicates time to activate Auto Change.
-
X
A29
A51D
[Alternation
Select]
0-1
0
NO
No
X
1
Enable Motor Alternation
A30
A51E
[Alt. Set Time]
0-
6000
[m]
Sets the Motor Alternation time..
1
X
A31
A51F
[Alt. Delay
Time]
600.0
[sec]
Sets the Alternation Delay Time.
10
X
A32
A520
[Lead Pump
Select]
1-2
Select Lead Pump.
1
X
A33
A521
[Lead Pump
Display]
1-2
Pump Operation Time.
-
O
2)
: Set A11 to 1 (MMC Select) to display this parameter.
3)
: Set A23 to 1 (Auto Change Select) to display this parameter.
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...
Page 224: ...210 ...