194
Troubleshooting & Maintenance
Fault remedy
Protective functions & cause
Descriptions
EEP
: Parameter save error
HWT
: Hardware fault
Err
: Communication error
COM
: Keypad error
NTC
: NTC error
Contact your local LSIS sales
representative.
Overload Protection
12.2.1
IOLT : IOLT(inverter Overload Trip) protection is activated at 120% of the inverter rated
current for 1 minute and greater.
OLT : OLT is selected when F56 is set to 1 and activated at 200% of F57[Motor rated
current] for 60 sec in F58. This can be programmable.
iG5H is not provided with
“Overspeed Protection.”