Basic Functions
84
►
More precise time unit can be set corresponding to load characteristics as shown below.
►
In SV-iG5H, number display is available up to 5. Therefore, if time unit is set to 0.01 sec,
Max Accel/Decel time would be 600.00 sec.
Group
Code
Parameter Name
Setting
Range
Default
Unit
Function
group 2
H71
[Accel/Decel time
scale]
0
0.01-600.00 0.01
sec
1
0.1-6000.0
0.1
sec
2
1-60000
1
sec
Accel/Decel time setting based on Operating Frequency
7.4.2
Group
Code
Parameter Name
Setting
Range
Default
Unit
Drive
group
ACC
[Accel time]
-
0 - 6000
5.0
Sec
dEC
[Decel time]
-
0 - 6000
10.0
Sec
Function
group 2
H70
[Frequency
Reference for
Accel/Decel]
1
0 - 1
0
Accel/Decel time is set at the ACC/dEC.
If you set H70 to 1 {Delta frequency}, Accel/Decel time is the time that takes to reach a
target freq from constant run freq (Current operating freq.).
►
When H70 and Accel time are set to 1 {Delta frequency} and 5 sec, respectively,
►
The below graph in Section A shows the change in operating frequency when target
frequency is set to 10Hz at first and then changed to 30Hz.
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...
Page 224: ...210 ...