Protective functions
162
10.3 Stall prevention
Group
Code
Parameter Name
Setting
Range
Default
Unit
Function
group 1
F59
[Stall prevention select]
-
0 - 7
4
F60
[Stall prevention level]
-
30 - 200
130
%
I/O group
I54
[Multi-function relay1 select]
7
0 -30
12
I55
[Multi-function relay2 select]
7
17
During acceleration: Motor starts deceleration when current exceeding the value set in F60
flows.
During constant run: Motor decelerates when current exceeding the value set in F60 flows.
During deceleration: Motor deceleration is stopped when inverter DC link voltage rises
above a certain voltage level.
F60: The value is set as the percent of motor rated current (H33).
I54, I55: Inverter outputs signals through multi-function output terminal Relay1 or relay
output Relay2 or external sequence when stall prevention function is activated. Motor
stall status still can be monitored in these codes though F59 is not selected (000).
►
F59: Stall prevention can be set as the table below.
F59
Stall
prevention
Setting
During
Deceleration
During constant
speed
During
Acceleration
Bit 2
Bit 1
Bit 0
0
-
-
-
1
-
-
2
-
-
3
-
4
-
-
5
-
6
-
7
►
For example, set F59 to 3 to make stall prevention active during Acceleration and
constant run.
►
When stall prevention is executed during acceleration or deceleration, Accel/Decel time
may take longer than the user-setting time.
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...
Page 224: ...210 ...