FusionModule800 Smart Small Data Center
Maintenance Guide
3 Alarm References
Issue 02 (2016-11-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
15
Component
Alarm Name
Alarm
Severity
Possible
Cause
Measures
Comp drive
short period
Critical
A compressor
drive fault
occurs multiple
times or the
compressor
drive fault is
not rectified
within a long
time.
Maintain or
replace the
compressor
drive, and clear
the cumulative
runtime.
Indoor fan
failure
Critical
1.
The indoor
fan is faulty.
2.
Cables to
the indoor
fan are loose
or damaged.
1.
Maintain or
replace the
indoor fan.
2.
Check
cables to the
indoor fan.
EEV high
overheating
locked
Critical
1.
The
electronic
expansion
valve coil is
loose.
2.
The
electronic
expansion
valve coil is
faulty.
3.
The
electronic
expansion
valve is
faulty.
1.
Reinstall the
electronic
expansion
valve coil.
2.
Replace the
electronic
expansion
valve coil.
3.
Replace the
electronic
expansion
valve.
EEV auto
control fault
Critical
1.
The suction
pressure
sensor is
faulty.
2.
The suction
temperature
sensor is
faulty.
1.
Rectify the
fault of the
suction
pressure
sensor.
2.
Rectify the
fault of the
suction
temperature
sensor.
Indoor fan
malfunction in
high humidity
Critical
One or more
indoor fans are
faulty and the
ambient
humidity is
high.
Check and
replace faulty
indoor fans.