A Preventive Maintenance Table
Issue 02 (2016-11-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
114
Maintenance area
Item
Operation
Expected Result
Troubleshootin
g
UPS
Operating
environment
N/A
Ambient
temperature:
0–40°C
Humidity:
0–95% RH
(non-condensin
g)
If the humidity
and
temperature
are abnormal,
check the air
conditioner
status.
If the input
voltage is
abnormal,
check the
power grid
status and
input cable
connection.
Liquid crystal
display (LCD)
N/A
According to the
status icons on the
LCD, all units are
operating properly.
No fault or alarm
information is
found in the active
and historical
alarm records.
If an alarm is
present, rectify the
fault by checking
the device status
and parameters.
Battery
Battery management
alarm
N/A
No battery
management alarm
is generated.
Identify the cause
of an alarm based
on the alarm
information.
Battery appearance
N/A
1.
The surface is
clean and tidy
without stains.
2.
The battery
terminals are
intact.
3.
Batteries are
free from
damage and
cracks.
4.
Batteries are
free from acid
leakage.
5.
Batteries are
not deformed or
bulged.
If the battery
appearance is
abnormal, contact
Huawei technical
support.