Maintenance area
Item
Operation
Expected Result
Troubleshootin
g
N/A
Check that the wet
film and humidifier
water pan are clean
and have no scale.
If there is much
water scale,
replace the wet
film humidifier by
referring to
Replacing a Wet
Film Humidifier
N/A
Check that no
operating overtime
alarm is generated
on the humidifier.
Clean the wet film
humidifier with
water.
Indoor fan
N/A
Check that the
indoor fan guard is
not distorted.
Repair or replace
the fan guard if it
is distorted.
N/A
Check that the
indoor fan blades
are intact.
Replace the fan
component if it is
damaged.
N/A
Check that the
operating indoor
fan generates no
abnormal noise.
Replace the fan
component if it is
damaged.
N/A
Check that the
screws on the
indoor fan are not
loose or distorted.
Tighten loose
screws.
Compressor
N/A
Check that the
compressor is
secured.
Tighten screws if
the compressor is
not secured.
N/A
Check that the
operating
compressor
generates no
abnormal noise.
Replace the
compressor.
N/A
Check that the
refrigerant pipe is
free from oil stains
and rust.
Check for leaks
and repair the
pipe.
Refrigerant pipe and
water pipe
N/A
Check that the
water pipe is
tightened, free of
water leaks.
Check for leaks
and repair the
pipe, or reconnect
the pipe.
N/A
Check that the
thermal insulation
foam is intact.
Rewrap the
thermal insulation
foam.