FusionModule800 Smart Small Data Center
Maintenance Guide
5 Parts Replacement
Issue 02 (2016-11-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
68
Figure 5-31
Removing a wet film humidifier
Step 7
Install the new wet film humidifier in the original position by performing the preceding steps
in reverse order, and connect the hose.
Step 8
Clear up the wet film humidifier total runtime.
Method 1: Log in to the ECC800 mobile phone or pad app as admin.
a.
Choose
Home
.
b.
Tap the cabinet that houses the air conditioner in the micro-module view.
c.
Tap the air conditioner to be set in the cabinet layout diagram.
d.
Choose
Real-time Data
>
Perf Maint
, clear up the wet film humidifier total
running time.
Method 2: Log in to the ECC800 WebUI as admin. Choose
Monitoring
>
Air
Conditioner
>
NetCol5000-A0104
>
Controls
>
Performance Maint Ctrl
, clear up the
wet film humidifier total running time.
Step 9
After starting the air conditioner and ensuring that the water inlet pipe properly connects to
the wet film humidifier. Log in to the ECC800 WebUI as admin. Choose
Monitoring
>
Air
Conditioner
>
NetCol5000-A0104
>
Running Parameters
>
System Controls
>
Ctrl Info
,
choose
Humid
>
Enable
, and the click
Submit
.
----End
5.3.1.6 Replacing an Electric Heater
Prerequisites
Tools: Phillips screwdriver, diagonal pliers or scissors.