FusionModule800 Smart Small Data Center
Maintenance Guide
3 Alarm References
Issue 02 (2016-11-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
7
Component
Alarm Name
Alarm
Severity
Possible
Cause
Measures
UPS
Rectifier fault
Critical
The mains
has
experienced
a transient
high
voltage.
The output
carries
special loads
such as the
inductive
and
rectification
loads.
The output
carries the
transformer
load but the
transformer
mode is not
enabled.
The
hardware is
damaged.
Rectify the
fault, and
power on
the UPS
again.
Check that
the load
types are
supported
by the UPS.
Enable the
transformer
mode.
Contact
Huawei
technical
support.
Internal fault
Critical
The bypass
input cable
connection does
not match the
output system.
Correct the
bypass input
cable
connection so
that it matches
the output
system.
Fan fault
Critical
The fan is
abnormal.
Clean up
foreign matter
around the fan.
If the fault
persists, contact
Huawei
technical
support.