FusionModule800 Smart Small Data Center
Maintenance Guide
3 Alarm References
Issue 02 (2016-11-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
8
Component
Alarm Name
Alarm
Severity
Possible
Cause
Measures
Inverter fault
Critical
The inverter
output
short-circuits.
Eliminate the
short circuit at
the output port
cable
connection, and
then power on
and start the
inverter again.
If the fault
persists, contact
Huawei
technical
support.
Intelligent
battery
monitoring
system
Communication
Failure
Critical
The network
cable
communication
is interrupted.
Check the cable
connection to
the smart ETH
gateway.
BCB Tripping
Critical
The battery
has
discharged
to the
end-of-disch
arge (EOD)
threshold.
The battery
circuit
breaker
(BCB) box
is manually
disconnecte
d.
There is a
security risk
in the
battery loop.
Identify the
alarm cause,
rectify the fault,
and switch on
the BCB box.
Single Batt.
terminal off
Critical
A battery
terminal
screw is not
tightened.
The battery
terminal is
not properly
connected to
the
connector.
Check that
battery
terminal
screws are
tightened.
Check that
battery
terminals
are properly
connected to
connectors.