FusionModule800 Smart Small Data Center
Maintenance Guide
5 Parts Replacement
Issue 02 (2016-11-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
84
Figure 5-43
Position of the filter dryer
(1) Filter dryer
(2) Welding point
Step 6
Weld the new filter dryer to the pipe.
Step 7
Secure the new filter dryer using cable ties.
Step 8
Perform a leakage test with nitrogen again.
Step 9
After checking that the air conditioner does not leak, vacuumize the air conditioner and
charge refrigerant.
Step 10
Reinstall the left front panel and left rear panel.
----End
5.3.2.4 Replacing a High Pressure Sensor
Prerequisites
A high pressure sensor needs to be replaced.
A spare high pressure sensor of the same model is available and functional.
Context
Tools: Phillips screwdriver, refrigerant retrieval device (required based on local
conditions), nitrogen injection and pressure preservation tool, vacuumization tool,
refrigerant injection tool, adjustable wrench, and sealant.
Preparation: Power off the outdoor unit.