FusionModule800 Smart Small Data Center
Maintenance Guide
A Preventive Maintenance Table
Issue 02 (2016-11-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
140
Maintenance area
Item
Operation
Expected Result
Troubleshootin
g
Output voltage
N/A
Output voltage:
53.5 V DC
(tolerance ±5%)
If the output
voltage is
abnormal, check
the load power
and cable
connection.
Indicator
N/A
The indicator on
the PSU is steady
green.
Check the output
voltage and
determine whether
the PSU is faulty.
If the PSU is
faulty, replace it.
Fan
N/A
No abnormal noise
is generated.
If abnormal noise
is generated, clean
the fan.
Operating
environment
N/A
Ambient
temperature:
–20°C to +65°C
Humidity:
0–95% RH
(non-condensin
g)
If the humidity or
temperature is
abnormal, check
the air conditioner
status.
Monitoring module
indicator
N/A
The monitoring
module indicator is
steady green or
blinking green.
If the indicator is
off or any
abnormal
condition occurs,
see
Monitoring
System
Troubleshooting
to rectify the fault.
Network interface
indicator
N/A
The green indicator
is steady on, and
the yellow
indicator is
blinking.
Check the network
cable connection.