FusionModule800 Smart Small Data Center
Maintenance Guide
5 Parts Replacement
Issue 02 (2016-11-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
64
b.
Tap the cabinet that houses the air conditioner in the micro-module view.
c.
Tap the air conditioner to be set in the cabinet layout diagram.
d.
Choose
Real-time Data
>
OFF
.
Method 2: Log in to the ECC800 WebUI as admin. Choose
Monitoring
>
Air
Conditioner
>
NetCol5000-A0104
>
Controls
>
Ctrl Info
, set
On/off status on
EMS
>
Off
, and then click
Submit
.
0104
in
NetCol5000-A0104
is variable and subject to changes with the air conditioner connection
sequence. The displayed value prevails.
Step 2
Disconnect the power supply from the air conditioner control unit after the air conditioner
shuts down over the EMS.
Step 3
Remove the return air filter by referring to
5.3.1.1 Replacing a Return Air Filter
Step 4
Remove the top metal sheet of the condensate pump, as shown in
Figure 5-29
Removing a condensate pump
Step 5
Remove the hose clamps at the water inlet and outlet hoses of the condensate pump using a
Phillips screwdriver, remove the hoses and take out the pump, as shown in
Step 6
Install the new condensate pump in the original position by performing the preceding steps in
reverse order, connect the hoses, and install hose clamps.
Step 7
Clear up the condensate pump total running time.
Method 1: Log in to the ECC800 mobile phone or pad app as admin.