FusionModule800 Smart Small Data Center
Maintenance Guide
4 Troubleshooting
Issue 02 (2016-11-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
26
Cat
ego
ry
Sympt
om
Possible Cause
Measure
generate
s too
much
noise.
(It is
commo
n that
the
compres
sor
generate
s much
noise
when it
shuts
down.)
Refrigerant oil is
insufficient.
Add refrigerant oil.
4.3 Monitoring System Troubleshooting
Table 4-3
Common faults and troubleshooting for PSUs
Symptom
Possible Cause
Measure
The Power indicator (green)
is off.
No AC input
Check whether the AC input
is abnormal.
PSU fault
Replace the PSU.
The Alarm indicator
(yellow) is steady on.
Overtemperature protection
The ambient temperature
exceeds the upper
threshold. Increase the
cooling capacity of the
air conditioner.
The air channel is
blocked. Unblock it.
AC input overvoltage or
undervoltage protection
Check whether the AC input
is abnormal.
The Alarm indicator
(yellow) is blinking.
PSU communication failure
1.
Clean the connector in
the rear of the faulty
PSU.
2.
If the fault persists,
replace the ECC800
subrack.
Monitoring module
communication failure