FusionModule800 Smart Small Data Center
Maintenance Guide
A Preventive Maintenance Table
Issue 02 (2016-11-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
118
Maintenance area
Item
Operation
Expected Result
Troubleshootin
g
Operating
environment
N/A
Ambient
temperature:
–20°C to +65°C
Humidity:
0–95% RH
(non-condensin
g)
If the humidity or
temperature is
abnormal, check
the air conditioner
status.
Cable connections
N/A
The cable
connections are
secure.
Secure loose
cables.
N/A
Cables are not
damaged.
Replace damaged
cables.
Camera
Camera availability
On the ECC800
WebUI, click
Maintenance
>
View Video
>
Video Info
to enter
the video view
page. Type the
camera name or IP
address to find the
camera, and click
View
to view the
real-time
monitoring page.
The monitoring
page is properly
displayed after you
click
View
.
If the monitoring
page is not
displayed after
you click
View
,
check that the IP
address is
correctly set, and
check cable
connection or
replace the
camera. For
details, see
The Intelligent
Battery Monitoring
System
Battery management
alarm
N/A
No battery
management alarm
is generated.
Find the cause of
an alarm based on
the alarm
information.
Cleanliness
N/A
Wipe the battery
surface using a
piece of white
paper and the paper
does not turn black.
Remove dust from
the battery
surface.
Battery connection
N/A
Battery terminals
and cables are in
good contact.
Ensure that battery
terminals and
cables are in good
contact.
Ambient temperature
of the intelligent
battery monitoring
system
N/A
The ambient
temperature of the
intelligent battery
monitoring system
is lower than 45°C.
Find the cause of
an abnormal
temperature.