FusionModule800 Smart Small Data Center
Maintenance Guide
A Preventive Maintenance Table
Issue 02 (2016-11-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
126
Maintenance area
Item
Operation
Expected Result
Troubleshootin
g
Cables between
batteries
N/A
No cable
deteriorates and
the insulation layer
does not crack.
Replace the faulty
cable.
Battery voltage
N/A
Equalized
charging
voltage: 2.35
V/cell ± 0.02
V/cell.
Float charging
voltage: 2.25
V/cell ± 0.02
V/cell.
1.
Check whether
the equalized
charging
voltage and
float charging
voltage of a
battery are
normal.
2.
If the charging
voltage of a
battery exceeds
the
specifications
requirement,
perform a
complete
forcible
equalized
charging for
the battery, and
check again
whether the
voltage is
normal.
3.
If the fault
persists,
contact Huawei
technical
support.
Shallow discharge
test (recommended)
N/A
Conduct a shallow
discharge test
when the UPS is
backed up to verify
that the batteries
can discharge
normally.
1.
Locate the
cause when an
exception is
identified.
2.
If the fault
persists,
contact Huawei
technical
support.
ECC800
AC input
N/A
Input voltage:
200–240 V AC
Frequency: 45–55
Hz
If the input voltage
is abnormal, check
the power grid and
input cable
connection.