FusionModule800 Smart Small Data Center
Maintenance Guide
A Preventive Maintenance Table
Issue 02 (2016-11-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
123
Maintenance area
Item
Operation
Expected Result
Troubleshootin
g
Liquid crystal
display (LCD)
N/A
According to the
status icons on the
LCD, all units are
operating properly.
No fault or alarm
information is
found in the active
and historical
alarm records.
If an alarm is
present, rectify the
fault by checking
the device status
and parameters.
Cleanliness
N/A
Wipe the cabinet
surface using a
white paper and
the paper does not
turn black.
Remove the dust,
especially from
the front panel.
Parameter
configuration
N/A
The configuration
of the output
voltage grade,
frequency, number
of batteries, and
battery capacity
meets
requirements.
Reset the
parameters.
Power cables and
terminals (between
the UPS and the
power distribution
subrack)
N/A
The insulation
layer of cables is
intact and
terminals are free
from signs of
ignition.
Replace the
cables.
Secure output
terminals.
Battery
Battery management
alarm
N/A
No battery
management alarm
is generated.
Identify the cause
of an alarm based
on the alarm
information.
Battery appearance
N/A
1.
The surface is
clean and tidy
without stains.
2.
The battery
terminals are
intact.
3.
Batteries are
free from
damage and
cracks.
4.
Batteries are
free from acid
leakage.
5.
Batteries are
not deformed or
bulged.
If the battery
appearance is
abnormal, contact
Huawei technical
support.