FusionModule800 Smart Small Data Center
Maintenance Guide
A Preventive Maintenance Table
Issue 02 (2016-11-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
129
Maintenance area
Item
Operation
Expected Result
Troubleshootin
g
The Intelligent
Battery Monitoring
System
Battery management
alarm
N/A
No battery
management alarm
is generated.
Find the cause of
an alarm based on
the alarm
information.
Cleanliness
N/A
Wipe the battery
surface using a
piece of white
paper and the
paper does not turn
black.
Remove dust from
the battery surface.
Battery connection
N/A
Battery terminals
and cables are in
good contact.
Ensure that battery
terminals and
cables are in good
contact.
Ambient temperature
of the intelligent
battery monitoring
system
N/A
The ambient
temperature of the
intelligent battery
monitoring system
is lower than 45°C.
Find the cause of
an abnormal
temperature.
The Water Sensor
and Water Detection
Rope
Water sensor and
water detection rope
function
Place the water
detection rope into
the water and check
whether a water
leakage alarm is
generated by the
water sensor.
A water leakage
alarm is generated.
If no water
leakage alarm is
generated, replace
the water detection
rope by referring
to
Replacing a Water
Sensor and Water
Detection Rope
The Cooling System
Water pan filter
N/A
Check that the
water pan filter is
clean and not
blocked.
Clean it with
water.
Condensate pan and
liquid level detector
N/A
Check that the
condensate pan
and liquid level
detector have no
dirt or scale.
Clean up the dirt
and scale from the
condensate pan
and liquid level
detector.
Humidifier float
N/A
Check that the
humidifier float
has no dirt or scale.
Clean up the dirt
and scale from the
humidifier float.
Return air filter
N/A
Check that the
return air filter is
clean and not
blocked.
Clean the air filter
with water
(recommended).