Procedure
Step 1
Shut down the air conditioner over the EMS.
Method 1: Log in to the ECC800 mobile phone or pad app as admin.
a.
Choose
Home
.
b.
Tap the cabinet that houses the air conditioner in the micro-module view.
c.
Tap the air conditioner to be set in the cabinet layout diagram.
d.
Choose
Real-time Data
>
OFF
.
Method 2: Log in to the ECC800 WebUI as admin. Choose
Monitoring
>
Air
Conditioner
>
NetCol5000-A0104
>
Controls
>
Ctrl Info
, set
On/off status on
EMS
>
Off
, and then click
Submit
.
0104
in
NetCol5000-A0104
is variable and subject to changes with the air conditioner connection
sequence. The displayed value prevails.
Step 2
Disconnect the power supplies from the air conditioner control unit and the outdoor unit after
the air conditioner shuts down over the EMS.
Step 3
Open the top cover, front panel, and left front panel using a screwdriver, as shown in
Figure 5-40
Removing a panel
Step 4
Cut the cable ties on the fan cable using diagonal pliers and take out the outdoor fan cable
from the electric control box.