FusionModule800 Smart Small Data Center
Maintenance Guide
5 Parts Replacement
Issue 02 (2016-11-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
112
Figure 5-74
Connecting a conversion cable to a water detector
Step 2
Replace a water detection rope.
1.
Remove the faulty water detection rope from the port.
2.
Install a new water detection rope, as shown in
Figure 5-75
Connecting a new water detection rope
(1) Conversion cable end B, connecting to
the water detection rope
(2) Water detection rope end A, connecting
to the conversion cable
The water detection rope and conversion cable are interconnected through the male and female
connectors.
----End
Follow-up Procedure
Check whether the new water detector works properly. Connect the network cable between
the water detector and ECC800, immerse the water detection cable in water, and check
whether an alarm is generated. If an alarm is generated, the replacement is complete.