FusionModule800 Smart Small Data Center
Maintenance Guide
A Preventive Maintenance Table
Issue 02 (2016-11-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
128
Maintenance area
Item
Operation
Expected Result
Troubleshootin
g
Monitor interface
(network
management system
or Web)
N/A
Export air
conditioner logs,
alarms,
temperature,
humidity, as well
as the operating
status and time of
the water sensor,
door status sensor,
temperature
sensor, and smoke
sensor from the
monitoring system.
View the historical
alarms generated
in this quarter and
select the most
common five ones.
Rectify faults if an
alarm is generated
by referring to
and
Monitoring
System
Troubleshooting
or contact Huawei
technical support.
Operating
environment
N/A
Ambient
temperature:
–20°C to
+65°C
Humidity:
0–95% RH
(non-condensin
g)
If the humidity or
temperature is
abnormal, check
the air conditioner
status.
Cable connections
N/A
The cable
connections are
secure.
Secure loose
cables.
N/A
Cables are not
damaged.
Replace damaged
cables.
Camera
Camera availability
On the ECC800
WebUI, click
Maintenance
>
View Video
>
Video Info
to enter
the video view
page. Type the
camera name or IP
address to find the
camera, and click
View
to view the
real-time
monitoring page.
The monitoring
page is properly
displayed after you
click
View
.
If the monitoring
page is not
displayed after
you click
View
,
check that the IP
address is
correctly set, and
check cable
connection or
replace the
camera. For
details, see