FusionModule800 Smart Small Data Center
Maintenance Guide
3 Alarm References
Issue 02 (2016-11-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5
3
Alarm References
This section provides only measures to clear the Smart Module major and critical alarms. For details
about other alarms, download them from the ECC800 WebUI.
Table 3-1
Alarm list
Component
Alarm Name
Alarm
Severity
Possible
Cause
Measures
Surge
protective
device (SPD)
SPD fault
Major
A surge
protection
module is
damaged or the
SPD circuit
breaker has
tripped.
Replace the
surge protection
module or
switch on the
SPD circuit
breaker.
Automatic
transfer switch
(ATS)
ATS No
Voltage (alarm
1 on the
display)
Major
The ATS
upstream
switch is not
turned on.
The
controller
power cable
is not
connected.
The input
power cable
is loose or
not
connected.
1.
Check that
the upstream
switch is
turned on.
2.
Check that
the
controller
power cable
is securely
connected.
3.
Check that
the input
power cable
is properly
connected.