FusionModule800 Smart Small Data Center
Maintenance Guide
3 Alarm References
Issue 02 (2016-11-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
11
Component
Alarm Name
Alarm
Severity
Possible
Cause
Measures
Supply-air HT
Critical
1.
The thermal
load power
is high or
the cooling
capacity is
insufficient.
2.
The supply
air
temperature
is higher
than the
upper
threshold
during
startup.
3.
The ambient
temperature
exceeds the
upper
threshold.
4.
The supply
air high
temperature
alarm
threshold is
inappropriat
e.
5.
The
temperature
displayed on
the LCD is
different
from the
actual
temperature.
1.
Add air
conditioners
.
2.
Check
whether
other causes
exist if the
alarm is not
cleared in a
long period
after startup.
3.
Measure the
ambient
temperature.
4.
Adjust the
supply air
high
temperature
alarm
threshold.
5.
Calibrate or
replace the
temperature
sensor.