FusionModule800 Smart Small Data Center
Maintenance Guide
5 Parts Replacement
Issue 02 (2016-11-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
108
Figure 5-69
Removing a smoke detector
Step 2
Remove the cables from the smoke detector and apply insulation measures such as wrapping
the cables with insulation tape to avoid hazards.
Step 3
Install a new smoke detector and reconnect the cables.
Step 4
Install the new smoke detector to the base by rotating it in a direction opposite to
----End
Follow-up Procedure
Check whether the new smoke detector works properly. If its status is displayed on the WebUI
of the ECC800, the new smoke detector works properly.
5.4.15 Replacing a Water Sensor and Water Detection Rope
Prerequisites
Recommended tools and materials: Phillips screwdriver, crimping tool
A water sensor needs to be replaced.
A spare water sensor of the same model is available and functional.
Context
The water detector is installed in the Converged Cabinet and bound to the rack rail using
cable ties. The binding position is 5 U away from the cabinet bottom, as shown by (2) in