FusionModule800 Smart Small Data Center
Maintenance Guide
3 Alarm References
Issue 02 (2016-11-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
10
Component
Alarm Name
Alarm
Severity
Possible
Cause
Measures
Air conditioner
Return-air HT
Critical
1.
The thermal
load power
is high or
the cooling
capacity is
insufficient.
2.
The return
air
temperature
is higher
than the
upper
threshold
during
startup.
3.
The ambient
temperature
exceeds the
upper
threshold.
4.
The return
air high
temperature
alarm
threshold is
inappropriat
e.
5.
The
temperature
displayed on
the LCD is
different
from the
actual
temperature.
1.
Add air
conditioners
.
2.
Check
whether
other causes
exist if the
alarm is not
cleared in a
long period
after startup.
3.
Measure the
ambient
temperature.
4.
Adjust the
return air
high
temperature
alarm
threshold.
5.
Calibrate or
replace the
temperature
sensor.
Floor water
overflow
Critical
1.
There is
water on the
floor.
2.
The
overflow
detection
board is
faulty.
1.
Check and
clear the
water from
the water
pan.
2.
Maintain or
replace the
overflow
detection
board.