FusionModule800 Smart Small Data Center
Maintenance Guide
5 Parts Replacement
Issue 02 (2016-11-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
85
Procedure
Step 1
Shut down the air conditioner over the EMS.
Method 1: Log in to the ECC800 mobile phone or pad app as admin.
a.
Choose
Home
.
b.
Tap the cabinet that houses the air conditioner in the micro-module view.
c.
Tap the air conditioner to be set in the cabinet layout diagram.
d.
Choose
Real-time Data
>
OFF
.
Method 2: Log in to the ECC800 WebUI as admin. Choose
Monitoring
>
Air
Conditioner
>
NetCol5000-A0104
>
Controls
>
Ctrl Info
, set
On/off status on
EMS
>
Off
, and then click
Submit
.
0104
in
NetCol5000-A0104
is variable and subject to changes with the air conditioner connection
sequence. The displayed value prevails.
Step 2
Disconnect the power supplies from the air conditioner control unit and the outdoor unit after
the air conditioner shuts down over the EMS.
Step 3
Open the top cover and right rear panel.
Step 4
Cut the cable ties on the high pressure sensor cable using diagonal pliers and take out the high
pressure sensor cable from the electric control box.
Step 5
Remove the high pressure sensor using an adjustable wrench.
of the high pressure sensor.
Step 6
Apply sealant to the threads to be connected. Install the new high pressure sensor in the
original position using an adjustable wrench and connect cables.
Step 7
Secure the high pressure sensor cable using cable ties.
Step 8
Check the high pressure sensor and the system do not leak.
Step 9
Reinstall the right rear panel and top cover.
----End
5.3.2.5 Replacing an Oil Heating Belt
Prerequisites
The oil heating belt needs to be replaced.
A spare oil heating belt of the same model is available and functional.
Context
Tools: Phillips screwdriver, cable ties, diagonal pliers.
Preparation: Power off the outdoor unit.
Procedure
Step 1
Shut down the air conditioner over the EMS.
Method 1: Log in to the ECC800 mobile phone or pad app as admin.