5.3.1.8 Replacing a Humidifier Float
For the method of replacing a humidifier float, see
5.3.1.7 Replacing a Liquid Level Detector
5.3.1.9 Replacing a Differential Pressure Switch
Prerequisites
Tool: Phillips screwdriver.
The differential pressure switch needs to be replaced.
A spare differential pressure switch of the same model is available and functional.
Context
The differential pressure switch is maintained from the rear.
Procedure
Step 1
Shut down the air conditioner over the EMS.
Method 1: Log in to the ECC800 mobile phone or pad app as admin.
a.
Choose
Home
.
b.
Tap the cabinet that houses the air conditioner in the micro-module view.
c.
Tap the air conditioner to be set in the cabinet layout diagram.
d.
Choose
Real-time Data
>
OFF
.
Method 2: Log in to the ECC800 WebUI as admin. Choose
Monitoring
>
Air
Conditioner
>
NetCol5000-A0104
>
Controls
>
Ctrl Info
, set
On/off status on
EMS
>
Off
, and then click
Submit
.
0104
in
NetCol5000-A0104
is variable and subject to changes with the air conditioner connection
sequence. The displayed value prevails.
Step 2
Disconnect the power supply from the air conditioner control unit after the air conditioner
shuts down over the EMS.
Step 3
Remove the return air filter by referring to
5.3.1.1 Replacing a Return Air Filter
Step 4
Remove the two screws from the differential pressure switch fastener, and remove the
differential pressure tube, as shown in