FusionModule800 Smart Small Data Center
Maintenance Guide
A Preventive Maintenance Table
Issue 02 (2016-11-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
122
Quarterly preventive maintenance table
Table A-2
Quarterly preventive maintenance table
Maintenance area
Item
Operation
Expected Result
Troubleshootin
g
Power Distribution
System
Power indicators
Check the
indicators.
All indicators are
normal.
The power supply
is normal. Replace
the indicator that
generates no or
dim light.
Surge protection
module
Check the surge
protection module
indicator and
miniature circuit
breaker (MCB)
status.
The surge
protection
module
indicator is
steady green.
The MCB is
ON.
If the surge
protection
module
indicator is
steady red,
replace the
surge
protection
module.
If the MCB is
OFF, switch it
on.
Emergency fan
Check whether the
top of the
emergency fan is
blocked.
The top of the fan
is clean and not
blocked.
Clean dust and
foreign matters
from the top of the
fan.
UPS
Operating
environment
N/A
Ambient
temperature:
0–40°C
Humidity:
0–95% RH
(non-condensin
g)
If the humidity
and
temperature are
abnormal,
check the air
conditioner
status.
If the input
voltage is
abnormal,
check the
power grid
status and input
cable
connection.