Component
Alarm Name
Alarm
Severity
Possible
Cause
Measures
Single Batt.
Exception
Critical
The battery
shell is
broken,
resulting in
electrolyte
and
electricity
leakage.
The battery
loop cable is
broken and
short-circuit
ed to the
ground,
resulting in
electricity
leakage.
Check
whether the
appearances
of abnormal
batteries are
intact, and
replace
abnormal
batteries.
Check
whether
battery loop
cables are
deteriorated
or broken,
and replace
faulty
cables.