FusionModule800 Smart Small Data Center
Maintenance Guide
A Preventive Maintenance Table
Issue 02 (2016-11-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
133
Yearly preventive maintenance table
Table A-3
Yearly preventive maintenance table
Maintenance area
Item
Operation
Expected Result
Troubleshootin
g
Power Distribution
System
Power indicators
Check the
indicators.
All indicators are
normal.
The power supply
is normal. Replace
the indicator that
generates no or
dim light.
Surge protection
module
Check the surge
protection module
indicator and
miniature circuit
breaker (MCB)
status.
The surge
protection
module
indicator is
steady green.
The MCB is
ON.
If the surge
protection
module
indicator is
steady red,
replace the
surge
protection
module.
If the MCB is
OFF, switch it
on.
Emergency fan
Check whether the
top of the
emergency fan is
blocked.
The top of the fan
is clean and not
blocked.
Clean dust and
foreign matters
from the top of the
fan.
Dust inside the
power distribution
subrack
Check whether
there is dust on the
power distribution
subrack panel.
The white paper
that you use to
wipe the cabinet
panel is clean.
If the white paper
is dirty, clean the
power distribution
subrack.
Bolts between power
cables and the
busbar after
power-off
Tighten all bolts
regularly using an
adjustable wrench.
The bolts are
secured.
Tighten a bolt if it
is loose.