Upgrade and Maintenance Manual - English

FUJITSU Server PRIMERGY TX1330 M1 

Upgrade and Maintenance Manual

October 2014

Summary of Contents for Server PRIMERGY TX1330 M1

Page 1: ...Upgrade and Maintenance Manual English FUJITSU Server PRIMERGY TX1330 M1 Upgrade and Maintenance Manual October 2014 ...

Page 2: ...on mbH www cognitas de Copyright 2014 Fujitsu Technology Solutions GmbH All rights reserved Delivery subject to availability right of technical modifications reserved All hardware and software names used are trademarks of their respective manufacturers The contents of this manual may be revised without prior notice Fujitsu assumes no liability for damages to third party copyrights or other rights ...

Page 3: ...of these components beyond their operating life may result in electrolyte leakage or depletion potentially causing emission of foul odor or smoke As a guideline in a normal office environment 25 C operating life is not expected to be reached within the maintenance support period 5 years However operating life may be reached more quickly if for example the product is used in a hot environment The c...

Page 4: ...l Computer issued by JEITA the Japan Electronics and Information Technology Industries Association Technology controlled by the Foreign Exchange and Foreign Trade Control Law of Japan Documents produced by Fujitsu may contain technology controlled by the Foreign Exchange and Foreign Trade Control Law of Japan Documents which contain such technology should not be exported from Japan or transferred ...

Page 5: ...and Maintenance Manual Only for the Japanese market I Although described in this manual some sections do not apply to the Japanese market These options and routines include CSS Customer Self Service USB Flash Module UFM ...

Page 6: ...Upgrade and Maintenance Manual TX1330 M1 Version history Issue number Reason for update 1 0 August 2014 Initial release 1 1 October 2014 Corrected cabling table ...

Page 7: ...at hand 28 3 Important information 31 3 1 Safety instructions 31 3 2 ENERGY STAR 39 3 3 CE conformity 39 3 4 FCC Class A Compliance Statement 40 3 5 Environmental protection 41 4 Basic hardware procedures 43 4 1 Using diagnostics information 43 4 1 1 Locating the defective server 43 4 1 2 Determining the error class 44 4 1 2 1 Global Error indicator 44 4 1 2 2 Customer Self Service CSS indicator 4...

Page 8: ...er 59 4 5 1 3 Mounting the server in the rack 60 4 5 1 4 Sliding the server into the rack 62 4 5 2 Tower model 63 4 5 2 1 Installing the front cover 63 4 5 2 2 Installing the HDD bay cover 64 4 5 2 3 Installing the side cover 65 4 5 2 4 Locking the server 66 4 6 Connecting the server to the mains 67 4 7 Switching on the server 68 5 Basic software procedures 69 5 1 Starting the maintenance task 69 ...

Page 9: ...ring the System Event Log SEL 87 5 2 11 1 Viewing the SEL 87 5 2 11 2 Clearing the SEL 88 5 2 12 Updating the NIC configuration file in a Linux environment 88 5 2 13 Enabling BitLocker functionality 90 5 2 14 Performing a RAID array rebuild 90 5 2 15 Looking up changed MAC WWN addresses 91 5 2 15 1 Looking up MAC addresses 91 5 2 15 2 Looking up WWN addresses 92 5 2 16 Using the Chassis ID Prom To...

Page 10: ... the power distribution board 113 6 3 4 1 Preliminary steps 113 6 3 4 2 Removing the hot plug power supply units 113 6 3 4 3 Replacing the defective power distribution board 114 6 3 4 4 Installing the hot plug power supply units 115 6 3 4 5 Concluding steps 116 6 4 Converting a standard power supply to a redundant power supply 116 6 4 1 Preliminary steps 116 6 4 2 Removing the standard power suppl...

Page 11: ...ing order 133 7 3 2 HDD naming scheme 133 7 3 3 Installing 3 5 inch HDD modules 133 7 3 3 1 Preliminary steps 134 7 3 3 2 Removing a 3 5 inch HDD dummy module 134 7 3 3 3 Installing a 3 5 inch HDD module 135 7 3 3 4 Concluding steps 136 7 3 4 Removing 3 5 inch HDD modules 137 7 3 4 1 Preliminary steps 137 7 3 4 2 Removing a 3 5 inch HDD module 138 7 3 4 3 Installing a 3 5 inch HDD dummy module 139...

Page 12: ...acket 162 9 2 2 Removing a slot bracket 168 9 3 Handling SFP transceiver modules 169 9 3 1 Installing SFP transceiver modules 169 9 3 2 Removing an SFP transceiver module 172 9 4 Expansion cards and riser card 175 9 4 1 Installing expansion cards 175 9 4 1 1 Preliminary steps 175 9 4 1 2 Removing the PCI slot bracket 176 9 4 1 3 Installing an expansion card 177 9 4 1 4 Concluding steps 178 9 4 2 R...

Page 13: ...ter cable to the TFM 196 9 5 2 6 Concluding steps 196 9 5 3 Installing a BBU 197 9 5 3 1 Preliminary steps 197 9 5 3 2 Connecting the BBU cable to the BBU 197 9 5 3 3 Installing the BBU in the holder 198 9 5 3 4 Installing the BBU holder into the chassis 198 9 5 3 5 Connecting the BBU cable to a controller 198 9 5 3 6 Concluding steps 199 9 5 4 Removing an FBU 200 9 5 4 1 Preliminary steps 200 9 5...

Page 14: ...liminary steps 213 10 3 2 Installing a memory module 213 10 3 3 Concluding steps 214 10 4 Replacing memory modules 214 10 4 1 Preliminary steps 214 10 4 2 Removing the defective memory module 215 10 4 3 Installing the new memory module 215 10 4 4 Concluding steps 215 11 Processors 217 11 1 Basic information 218 11 2 Upgrading or replacing the processor 218 11 2 1 Preliminary steps 218 11 2 2 Remov...

Page 15: ...abling of RDX drive 239 12 2 6 Concluding steps 240 12 3 Removing accessible drives 241 12 3 1 Preliminary steps 241 12 3 2 Removing an accessible drive 241 12 3 3 Installing accessible drive dummy covers 243 12 3 4 Concluding steps 244 12 4 Replacing accessible drives 245 12 4 1 Preliminary steps 245 12 4 2 Removing the defective accessible drive 245 12 4 3 Installing the new accessible drive 246...

Page 16: ...defective UFM 261 14 3 3 3 Installing the new UFM 262 14 3 3 4 Concluding steps 263 14 3 3 5 Software configuration 264 14 4 Trusted Platform Module TPM 264 14 4 1 Installing the TPM 264 14 4 1 1 Preliminary steps 264 14 4 1 2 Installing the TPM 265 14 4 1 3 Concluding steps 267 14 4 2 Removing the TPM 268 14 4 2 1 Preliminary steps 268 14 4 2 2 Removing the TPM 269 14 4 2 3 Concluding steps 271 1...

Page 17: ...intrusion switch cable 314 16 3 4 Concluding steps 316 17 Appendix 317 17 1 Mechanical overview 317 17 1 1 Server front 317 17 1 2 Server rear 319 17 1 3 Server interior 320 17 2 Connectors and indicators 322 17 2 1 Connectors and indicators on the system board 322 17 2 1 1 Onboard connectors 322 17 2 1 2 Onboard indicators and controls 324 17 2 1 3 I O panel connectors 326 17 2 1 4 I O panel indi...

Page 18: ...Upgrade and Maintenance Manual TX1330 M1 Content ...

Page 19: ...ing defective hardware components This manual focuses on on site maintenance tasks It is recommended to prepare each service assignment following remote diagnostics procedures as described in the ServerView Suite Local Service Concept LSC manual see section Documents you need at hand on page 28 V CAUTION The document at hand comprises procedures of a wide range of complexity Check the profile of q...

Page 20: ...at are being emphasized Ê describes activities that must be performed in the order shown Abc indicates keys on the keyboard V CAUTION Pay particular attention to texts marked with this symbol Failure to observe this warning may endanger your life destroy the system or lead to the loss of data I indicates additional information notes and tips indicates the procedure category in terms of complexity ...

Page 21: ... Suite management software and the iRMC web frontend to prepare hardware expansions ServerView Suite documentation is available online at http manuals ts fujitsu com http jp fujitsu com platform server primergy manual for the Japanese market Please refer to the following ServerView Suite topics Operation Virtualization Maintenance Out Of Band Management I For the latest information on hardware opt...

Page 22: ...rs and indicators on the front panel on page 329 If the defective component is a customer replaceable unit included in the CSS concept Customer Self Service only available for EMEA market the CSS indicators on the front and rear side of the server will light up For further information refer to the ServerView Suite Local Service Concept LSC manual available online at http manuals ts fujitsu com EME...

Page 23: ...nents that are handled as Customer Replaceable Units Hot plug power supply units Hot plug fan modules Hot plug HDD SSD modules Peripherals that are handled as Customer Replaceable Units Keyboard Mouse 2 1 2 Upgrade and Repair Units URU Upgrade and Repair Units are non hot plug components that can be ordered separately to be installed as options Upgrade Units or are available to the customer throug...

Page 24: ... hot plug hard disk drives 2 1 3 Field Replaceable Units FRU Removing and installing Field Replaceable Units involves complex maintenance procedures on integral server components Procedures will require shutting down opening and disassembling the server V CAUTION Maintenance procedures involving Field Replaceable Units must be performed exclusively by Fujitsu service personnel or technicians train...

Page 25: ... included Explanation Server shutdown no Shutdown time depends on hardware and software configuration and may vary significantly Software tasks necessary before maintenance are described in section Starting the maintenance task on page 69 Rack removal disassembly yes Making the server available removing the server from the rack if applicable Transport no Transporting the server to the service tabl...

Page 26: ...are and software configuration and may vary significantly Screw driver Bit insert Screw Usage Type Phillips PH2 No 2 hexagonal cross SW5 Ph2 Backupdrives optical disk drives chassis M3 x 3 5 mm black C26192 Y10 C151 Phillips PH2 No 2 hexagonal cross SW5 PZ2 System board M3 x 6 mm silver C26192 Y10 C68 Phillips PH2 No 2 hexagonal cross SW5 PZ2 Backup drives with UNC thread UNC 6 32 x 4 76 mm black ...

Page 27: ...dicated TPM screw driver TPM module fixing tool for the Japanese market TPM screw One way head black REM 3 x 15 mm black C26192 Y10 C176 Phillips PH1 No 1 TFM M2 5 x 4 mm silver C26192 Y10 C103 Phillips PH1 No 1 UFM nylon screw M3 x 4 5 mm white A3C40109082 Screw driver Bit insert Screw Usage Type Table 2 List of required tools and used screws ...

Page 28: ...Description Quick Start Hardware PRIMERGY TX1330 M1 leaflet Quick installation poster for initial operation available online ServerView Quick Start Guide ServerView クイックスタート ガイド for the Japanese market Information on initial server setup and software configuration available online Safety notes and regulations manual 安全上のご注意 for the Japanese market Important safety information available online or a...

Page 29: ...ailable online Warranty manual 保証書 for the Japanese market Important information on warranty regulations recycling and service available online or as a printed copy Returning used devices manual Recycling and contact information available online or as a printed copy Service Desk leaflet サポート サービス for the Japanese market Additional documentation RAID documentation available online at http manuals t...

Page 30: ...30 Upgrade and Maintenance Manual TX1330 M1 Before you start ...

Page 31: ...s a person who is trained to install the server including hardware and software Repairs to the device that do not relate to CSS failures shall be performed by service personnel Please note that unauthorized interference with the system will void the warranty and exempt the manufacturer from all liability Any failure to observe the guidelines in this manual and any improper repairs could expose the...

Page 32: ...to properly grounded power outlets or connected to the grounded rack internal power distribution system with tested and approved power cords Ensure that the device is connected to a properly grounded power outlet close to the device Ensure that the power sockets on the device and the properly grounded power outlets are easily accessible The On Off button or the main power switch if present does no...

Page 33: ...requirements and rules governing safety and electromagnetic compatibility and those relating to telecommunication terminals If you install other expansions they may damage the system or violate the safety regulations Information on which system expansions are approved for installation can be obtained from our customer service center or your sales outlet The components marked with a warning notice ...

Page 34: ...ent kind can cause a breakdown of equipment The installation indicated on this document is sometimes changed to the kind of possible options without notice Batteries Incorrect replacement of batteries may lead to a risk of explosion The batteries may only be replaced with identical batteries or with a type recommended by the manufacturer Do not throw batteries into the trash can Batteries must be ...

Page 35: ...ve equipment damage and can fly out of the device danger of injury particularly to uncovered body parts such as the face or neck High humidity and airborne dust levels are to be avoided Electric shocks and or server failures may be caused by liquids such as water or metallic items such as paper clips entering a drive Shocks and vibrations are also to be avoided Do not insert any objects other than...

Page 36: ...ot dry the CD DVD BD using devices such as a hair dryer To avoid dust damage and deformation keep the CD DVD BD in its case whenever it is not in use Do not store CDs DVDs BDs at high temperatures Areas exposed to prolonged direct sunlight or near heating appliances are to be avoided I You can prevent damage from the optical disk drive and the CDs DVDs BDs as well as premature wear of the disks by...

Page 37: ...atic electricity To ensure reliable protection you must wear an earthing band on your wrist when working with this type of module and connect it to an unpainted conducting metal part of the system Any devices or tools that are used must be free of electrostatic charge Wear a suitable grounding cable that connects you to the external chassis of the system unit Always hold components with ESDs at th...

Page 38: ...上のご注意 Never lift the server into the rack using the handles on the front panel When connecting and disconnecting cables observe the relevant instructions in the Important Information chapter of the technical manual for the corresponding rack The technical manual is supplied with the corresponding rack When installing the rack make sure that the anti tilt protection is correctly fitted For safety r...

Page 39: ...ses the properties guaranteed by ENERGY STAR can no longer be assured The ServerView Operations Manager user guide contains instructions for reading out measurement values including those relating to current energy consumption and air temperatures Either the Performance Monitor or the Task Manager can be used to read out CPU utilization levels The system complies with the requirements of the EC di...

Page 40: ...e harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between equipment and the receiver Connect the equipment into an outlet on a circuit different from that to which the ...

Page 41: ...constantly switched on should be switched off until they are needed as well as during long breaks and after completion of work Packaging information This packaging information doesn t apply to the Japanese market Do not throw away the packaging You may need it later for transporting the system If possible the equipment should only be transported in its original packaging Information on handling co...

Page 42: ...ing used devices manual via your local Fujitsu branch or from our recycling center in Paderborn Fujitsu Technology Solutions Recycling Center D 33106 Paderborn Tel 49 5251 525 1410 Fax 49 5251 525 32 1410 The device must not be disposed of with domestic waste This device is labeled in compliance with European directive 2002 96 EC on waste electrical and electronic equipment WEEE This directive set...

Page 43: ...logs are available online at http manuals ts fujitsu com illustrated_spares EMEA market only Perform the following diagnostics procedures to identify defective servers and components 4 1 1 Locating the defective server When working in a datacenter environment switch on the ID indicator on the front and rear connector panels of the server for easy identification see section Connectors and indicator...

Page 44: ...o light up in standby mode and after a server restart due to a power failure 4 1 2 1 Global Error indicator Ê Check the Global Error indicator on the front or connector panel of the server see section Connectors and indicators on page 322 Ê For further diagnostics proceed as follows Hardware errors Check the System Event Log SEL as described in section Viewing the SEL on page 87 Software agent rel...

Page 45: ...icate if the defective component is a customer or field replaceable unit see section Determining the error class on page 44 4 1 3 2 Local diagnostic indicators on the system board Using the Indicate CSS button Ê Shut down and power off the server Ê Disconnect the AC power cord from the system I It is mandatory to disconnect power cords in order to use the Indicate CSS functionality Ê Press the Ind...

Page 46: ... applications Ê Perform the required procedures described in the preliminary steps of each upgrade or maintenance task Ê Shut down the server I If the system is running an ACPI compliant operating system pressing the On Off button will perform a graceful shutdown Ê Switch on the ID indicator on the front and rear connector panels of the server as described in section Locating the defective server ...

Page 47: ...e outlet Failure to do so can cause electric shock In order to comply with applicable EMC regulations regulations on electromagnetic compatibility and satisfy cooling requirements the server must not run while the top side cover is removed For further safety information please refer to chapter Important information on page 31 4 4 1 Rack model 4 4 1 1 Extending the server out of the rack V CAUTION ...

Page 48: ...dicators on page 322 Ê If you are not using a cable mounting arm CMA kit ensure that the rear cables are long enough not to be strained or damaged when extending the server out of the rack Ê Fold down the two quick release levers 1 and pull the server out of the rack until it locks in place 2 V CAUTION Do not use the extended server as a surface on which to put things or as a work surface and stri...

Page 49: ...ck cabinet For the Japanese market please refer to 安全上のご注意 Additionally a lifter is required in the following cases The server weighs more than 50 kg The server weighs more than 21 kg and is installed above the height of 25 U When using a lifter this removal procedure needs to be carried out by maintenance personnel For configurations below 32 kg At least two people are needed to lift the server o...

Page 50: ... from the rack Ê Release the locking bars on both rails 1 Ê Lift up the front of the server as shown so that the front and middle rack mounting bolts are disengaged from the mounting points on the telescopic rails 2 Ê Lift the server out of the rear mounting points 3 and place it on an even surface ...

Page 51: ... Manual 51 Basic hardware procedures 4 4 1 3 Removing the top cover Figure 5 Removing the top cover rack server Ê Open the locking lever 1 This will slide the top cover back disengaging the locking mechanism 2 Ê Remove the top cover 3 ...

Page 52: ...t cover I You remove the rack front cover when installing removing accessible drives Figure 6 Removing the ID card rack server Ê Remove the ID card from the server Figure 7 Removing the rack front cover A Ê Remove two screws from the side brackets on either side of the rack mounting frame see circles ...

Page 53: ...rdware procedures Figure 8 Removing the rack front cover B Ê Carefully fold down and unhook the rack front cover 1 Ê Detach and remove the rack front cover from the chassis 2 4 4 2 Tower model 4 4 2 1 Removing the side cover Figure 9 Unlocking the server ...

Page 54: ...ver front Ê Turn the key clockwise to unlock the front and side covers 1 Ê Remove the key from the server front 2 and set aside for later use Figure 10 Removing the side cover tower server Ê Open the locking lever 1 This will slide the side cover back disengaging the locking mechanism 2 Ê Remove the side cover 3 ...

Page 55: ...55 Basic hardware procedures 4 4 2 2 Removing the HDD bay cover Figure 11 Removing the HDD cover Ê Unlock the server 1 Ê Pull out on the handle on the upper edge of the HDD bay cover Ê Fold out and remove the HDD bay cover from the front cover ...

Page 56: ...er I You remove the front cover when installing removing accessible drives converting a tower model to a rack model Figure 12 Removing the ID card tower server Ê Remove the ID card from the server front I It may be necessary to pull out on the ID card rather firmly However do not apply excessive force ...

Page 57: ...ic hardware procedures Figure 13 Removing the front cover tower server Ê Pinch the locking clips to disengage the front cover 1 while slightly pulling out Ê Carefully fold out the bottom end of the front cover 2 Ê Unhook and remove the front cover 3 ...

Page 58: ...ulations regulations on electromagnetic compatibility and satisfy cooling requirements the server must not run while the top side cover is removed For further safety information please refer to chapter Important information on page 31 4 5 1 Rack model 4 5 1 1 Installing the rack front cover Figure 14 Installing the rack front cover Ê Fit the rack front cover on the server front 1 Ê Carefully fold ...

Page 59: ...the ID card into its slot until it locks in place see close up in figure 6 on page 52 4 5 1 2 Installing the top cover Figure 15 Installing the top cover rack server Ê Check if the locking lever on the top cover is open Ê Lower the top cover onto the chassis recessed by 2 cm 1 Ê Close the locking lever on the top cover 2 This will slide the top cover shut engaging the locking mechanism 3 ...

Page 60: ...ighs more than 50 kg The server weighs more than 21 kg and is to be installed above the height of 25 U When using a lifter this installation procedure needs to be carried out by maintenance personnel For configurations below 32 kg At least two people are needed to lift the server into the rack cabinet For configurations below 55 kg At least three people are needed to lift the server into the rack ...

Page 61: ...further information refer to the Rack Mounting Kit RMK F2 Drop In Mounting Instructions Ê Fully extend the telescopic rails until they lock in place 1 Ê At a slight angle lower the server onto the rear mounting point on the telescopic rails 2 Ê Fold down the server 3 Ensure that the mounting bolts and the hooks are properly seated in the mounting points on the telescopic rails and that the locking...

Page 62: ...ils 1 Ê Slide the server inside the rack as far as it will go 2 until the quick release levers lock into place Ê Reconnect all cables except the power cord to the server rear I If you are not using a cable mounting arm CMA kit ensure that the rear cables are long enough not to be strained or damaged when extending the server out of the rack Use cable ties to prevent loose cables from blocking the ...

Page 63: ...4 5 2 1 Installing the front cover Figure 18 Installing the front cover tower server A Ê Hook the two tabs of the front cover into the notches in the chassis Figure 19 Installing the front cover tower server B Ê Fold down the front cover 1 until the locking clip on the bottom edge engage 2 ...

Page 64: ...ert and slide the ID card into its slot until it locks in place see figure 12 on page 56 4 5 2 2 Installing the HDD bay cover Figure 20 Installing the HDD bay cover Ê Insert the HDD bay cover into the front cover as shown 1 Ê Fold in the HDD bay cover until it locks in place 2 ...

Page 65: ... Installing the side cover tower server Ê Open the locking lever on the side cover Ê Fit the side cover on the chassis recessed by 2 cm 1 Ê Close the locking lever on the side cover 2 This will slide the top cover shut engaging the locking mechanism 3 Ê Reconnect all cables except the power cord to the server rear ...

Page 66: ...Maintenance Manual TX1330 M1 Basic hardware procedures 4 5 2 4 Locking the server Figure 22 Locking the server Ê If required by security regulations insert the key into the lock on the front panel and lock the server ...

Page 67: ...ancy the second power supply unit should be connected to a different AC power source from the other power supply unit If one AC power source should fail the server will still continue to run I It takes about 60 seconds until power on becomes possible Securing power cords Figure 23 Securing power cord Ê Loop the cable past the cable tie mounting bracket as shown 1 Ê Close the cable tie around the p...

Page 68: ...atisfy cooling requirements the server must not run while the top side cover is removed After connecting all power cords wait at least 60 seconds before pressing the On Off button Follow the safety instructions in chapter Important information on page 31 Ê Press the On Off button to start up the server Ê Ensure that the power on indicator above the On Off button is lit green Ê Perform the required...

Page 69: ... files Enable BitLocker again after the maintenance procedure is complete V CAUTION With BitLocker features enabled modifying the system configuration hardware or firmware settings may render the system inaccessible The system may enter Recovery Mode and require a 48 digits recovery password to return to normal operation Ensure to disable BitLocker drive encryption before maintaining the server Wh...

Page 70: ...so available in Japanese on the Fujitsu Extranet web pages 5 1 2 Disabling SVOM boot watchdog functionality The ServerView Operations Manager boot watchdog determines whether the server boots within a preset time frame If the watchdog timer expires the system will automatically reboot 5 1 2 1 Viewing boot watchdog settings Viewing boot watchdog settings in the BIOS Ê Enter the BIOS Ê Select the Se...

Page 71: ...re detailed information refer to the ServerView Operations Manager Server Management user guide 5 1 2 2 Configuring boot watchdog settings If the system is to be started from removable boot media for firmware upgrade purposes the Boot watchdog needs to be disabled before starting maintenance task Otherwise the Boot watchdog might initiate a system reboot before the flash process is complete V CAUT...

Page 72: ... or optical disk drive before removing it from the server Ê If the backup media cannot be ejected by conventional means and it is mandatory that the cartridge be removed prior to returning the drive for repair or disposing it a manual tape extraction needs to be performed For further information on forcible tape ejection please refer to the Tape Facts guide available to Fujitsu service partners fr...

Page 73: ...ujitsu service partners from the Fujitsu Extranet pages 5 1 5 Note on server maintenance in a Multipath I O environment When booting your server offline from the ServerView Suite DVD to perform an offline BIOS firmware update using the ServerView Update DVD or collect diagnostic data using PrimeCollect in a Multipath I O environment there is a risk of damaging the system configuration which may le...

Page 74: ... the Local System Update for PRIMERGY Servers user guide Ê Boot the server from the prepared Update DVD or USB stick DVD Ê Switch on the server Ê Right after switching on the server insert the Update DVD into the DVD drive and close the tray USB Ê Connect the USB stick to the server Ê Switch on the server If the server does not boot from DVD or USB stick proceed as follows Ê Reboot the server e g ...

Page 75: ... e g by pressing the reset button on the front or switching the server off and then on again after a few seconds Ê Once the server has been started press F12 to enter the boot menu Ê Use the Ê and Ë cursor keys to select your DVD drive as boot device and press ENTER The server will now boot from the ServerView Suite DVD Ê After the boot process is complete select your preferred GUI language Ê In t...

Page 76: ...ontrols and indicators on page 329 Using the iRMC web frontend Ê Enter the ServerView iRMC web frontend Ê Under System Overview click Identify LED On to switch on the ID indicators Using ServerView Operations Manager Ê In ServerView Operations Manager Single System View press the Locate button in the title bar to switch on the ID indicators 5 2 Completing the maintenance task 5 2 1 Updating or rec...

Page 77: ...uding the bootable iRMC firmware update image Ê Connect the USB stick to the USB port I Ensure that only the USB device with the iRMC firmware is connected to the USB port Remove all other USB devices temporarily Ê Restart the server Ê The system will detect the USB stick I If the BIOS cannot identify the USB stick the pop up message Failed to boot for Emergency flash Please Reset now will show up...

Page 78: ...ith the iRMC firmware is connected to the USB port Remove all other USB devices temporarily Ê Connect the server to the mains while pushing the ID button on the front panel Ask a second person to help you if necessary Ê Ensure that the Global Error indicator and the ID indicator are flashing to indicate that the server is entering the iRMC recovery state Ê Press the Power On Off button The system ...

Page 79: ...rder to verify whether the backup or restore process has been successful check the System Event Log SEL using the ServerView Operations Manager see also section Viewing and clearing the System Event Log SEL on page 87 After replacing the system board Ê Check the SEL log files as described in section Viewing and clearing the System Event Log SEL on page 87 to verify whether the backup data on the C...

Page 80: ...erverView Update Manager or Update Manager Express UME please refer to the following manuals ServerView Update Manager ServerView Update Management user guide ServerView Update Manager Express Local System Update for PRIMERGY Servers user guide Using the flash tool The latest firmware files are available as ASPs Autonomous Support Packages for Windows or as DOS tools from the Fujitsu support web p...

Page 81: ... desired PCI slot and set its Launch Slot OpROM setting to Enabled Ê Save your changes and exit the BIOS I Up to two Option ROMs can be activated in the system board BIOS at a time For detailed information on how to access the BIOS and modify settings refer to corresponding BIOS Setup Utility reference manual When the enabled expansion card is initialized during the POST phase of the boot sequence...

Page 82: ...e Fujitsu Extranet pages Re enabling backup drives If a backup drive has been disabled or deleted from the backup software drive list as described in section Verifying and configuring the backup software solution on page 73 it has to be re enabled to complete the maintenance task Ê Re enable backup drives and revise backup software settings and cronjobs I Detailed information on suitable backup so...

Page 83: ...o its default value Please take into account that the specified number of boot attempts can only be determined after this period of time If the customer knows about the original boot retry values proceed as follows to reset or configure the boot retry counter Resetting the boot retry counter in the BIOS Ê Enter the BIOS Ê Select the Server Mgmt menu Ê Under Boot Retry Counter press the or keys to ...

Page 84: ...the Integrated Remote Management Controller user guide 5 2 7 Enabling SVOM boot watchdog functionality If ServerView Operations Manager boot watchdog functionality has been disabled for firmware upgrade purposes see section Disabling SVOM boot watchdog functionality on page 70 it has to be re enabled to complete the maintenance task Timer settings can be configured in the BIOS or using the ServerV...

Page 85: ...tion After replacing the defective component it needs to be re enabled in the system board BIOS Ê Enter the BIOS Ê Select the Advanced menu Ê Select the status menu of the desired component Processors CPU Status I This option is only available for multi processor systems Memory Memory Status Expansion cards PCI Status Ê Reset replaced components to Enable Ê Save your changes and exit the BIOS I Fo...

Page 86: ...Linux environments After the system board has been replaced the system time is set automatically By default the RTC Real Time Clock time standard is set as the local time If a Linux OS is used and the hardware clock has been configured as UTC Universal Time Coordinated in the operating system the BMC local time may not be mapped correctly Ê After replacing the system board ask the system administr...

Page 87: ... the message type s you want to display Critical events Major events Minor events Informational events I Note on the SVOM Driver Monitor The Driver Monitor view gives you an overview of the monitored components as well as the associated events contained in the system event log on the managed server Under Monitored Components the monitored components are listed If a component has the status Warning...

Page 88: ...ose the Internal Event Log submenu Ê Under Internal Event Log Information click Clear Internal Event Log to clear the SEL I For detailed information on iRMC settings refer to the Integrated Remote Management Controller user guide 5 2 12 Updating the NIC configuration file in a Linux environment In order to prevent errors caused by changing network device names eth x it is recommended to store the ...

Page 89: ... and Ignore to complete the boot process Ê Use the vi text editor to specify the MAC address in the HWADDR section of the ifcfg eth x file I The MAC address can be found on the type label attached to the system board or network controller Example In order to modify the definition file for network controller 1 enter the following command vi etc sysconfig network scripts ifcfg eth1 In vi specify the...

Page 90: ...tup wizard available either from the Control Panel or Windows Explorer Ê Open Bitlocker Drive Encryption by clicking the Start button clicking Control Panel clicking Security and then clicking Bitlocker Drive Encryption I Administrator permission required If you are prompted for an administrator password or confirmation type the password or provide confirmation Ê To enable a temporarily disabled B...

Page 91: ... MAC WWN addresses When replacing a network controller the MAC Media Access Control and WWN World Wide Name addresses will change I In addition to the procedures described below MAC WWN addresses can also be found on the type label attached to a network controller or system board 5 2 15 1 Looking up MAC addresses Ê Enter the ServerView iRMC web frontend Ê Select the System Information menu Ê Under...

Page 92: ...form the customer about the changed WWN address QLogic FC adapters Ê Enable the network controller s Option ROM in the system board BIOS as described in section Enabling Option ROM scan on page 81 Ê Restart the server Ê During boot as soon as the QLogic BIOS utility option appears press ALT Q or CTRL Q Ê Under Select Host Adapter use the arrow keys æ Ë to select the desired FC FCoE adapter and pre...

Page 93: ...service ps Servers PRIMERGY Ê Select your PRIMERGY system from the main area of the page Ê From the categories selection choose Software Tools Documentation Ê In the Tools area click Tools Chassis IDProm Tool to download the file tool chassis Idprom Tool zip I For the Japanese market follow the instructions provided separately 5 2 17 Configuring LAN teaming Use ServerView Operations Manager to obt...

Page 94: ...rd LAN controller you have replaced has been used as part of a LAN teaming configuration Ê If LAN teaming has been active you will need to restore the configuration using the LAN driver utility after replacing the system board I For details refer to the relevant LAN driver manual 5 2 18 Switching off the ID indicator Press the ID button on the front panel or use the iRMC web frontend or ServerView...

Page 95: ...aintenance Tools Using the ServerView Installation Manager Ê Boot the system from the ServerView Suite DVD The ServerView Installation Manager is being started Ê Select your preferred user interface language Ê Under Status backup media select No status backup and click Continue Ê Select Maintenance Ê Select Server Configuration Manager Ê Check the box for rack model and save the setting by clickin...

Page 96: ... into the iRMC web interface Ê Under Sensors select Fans Ê Select the replaced fan in the system fans group and click Start Fan Test I For detailed information on iRMC settings refer to the Integrated Remote Management Controller user guide Executing the fan test via ServerView Operations Manager Ê Open the ServerView Operations Manager and log in Ê Under Administration select Server Configuration...

Page 97: ...t is complete restore the time setting to its initial value and click Save Page I For more detailed information refer to the ServerView Operations Manager user guide For the Japanese market Executing the fan test via Chassis ID Prom Tool I Please follow the instructions provided separately ...

Page 98: ...98 Upgrade and Maintenance Manual TX1330 M1 Basic software procedures ...

Page 99: ...manently built in The power supply unit adjusts automatically to any mains voltage in the range of 100 V 240 V or up to two hot plug power supply units slide in units In its basic configuration the server has one power supply unit that adjusts automatically to any mains voltage in the range of 100 V 240 V Besides the power supply unit a second power supply unit can be installed optionally to serve...

Page 100: ...steps Ê Disabling BitLocker functionality on page 69 Ê Locating the defective server on page 43 Ê Shutting down the server on page 46 Ê Disconnecting the server from the mains on page 46 Ê Getting access to the component on page 47 Ê Removing the fan module on page 151 Field Replaceable Unit FRU Hardware 10 minutes Tools Phillips PH2 No 2 screw driver ...

Page 101: ...rd power supply unit Figure 25 Disconnecting power cables A Ê Open the power cable clamp 1 Ê While pressing the release latch on the connector disconnect the ATX power supply connector 2 Figure 26 Disconnecting power cables B Ê Open the power clamp 1 Ê Disconnect the power management connector 2 ...

Page 102: ...upply Figure 27 Detaching the standard power supply unit Ê Remove the five screws see circles Figure 28 Taking out the standard power supply unit Ê Slide the power supply unit inside the chassis by 3 cm 1 Ê Lift the power supply unit out of the chassis 2 ...

Page 103: ...ower supply Figure 29 Removing the installation frame from the power supply unit A Ê Remove the two screws see circles Figure 30 Removing the installation frame from the power supply unit B Ê Remove the installation frame from the power supply unit ...

Page 104: ... power supply unit Figure 31 Attaching the installation frame to the power supply unit Ê Attach the installation frame to the power supply unit Figure 32 Securing the installation frame to the power supply unit Ê Secure the installation frame to the power supply unit with two screws see circles ...

Page 105: ...the rear of the chassis 2 Ê Secure the power supply unit to the chassis with five screws see figure 27 Ê Connect the ATX power supply connector to system board connector PWR1 see section Cabling plans on page 303 Ê Run the power cable through the power cable clamp see figure 25 Close the power cable clamp Ê Connect the power management connector to system board connector PC2009 see section Cabling...

Page 106: ...the server to the mains on page 67 Ê Switching on the server on page 68 Ê Enabling BitLocker functionality on page 90 Ê Performing a fan test after replacing a defective fan on page 96 6 3 Redundant power supply 6 3 1 Installing a hot plug power supply unit 6 3 1 1 Preliminary steps No steps needed Customer Replaceable Unit CRU Hardware 5 minutes Tools tool less ...

Page 107: ...mmy cover Ê Press in on both release latches 1 and remove the dummy cover 2 V CAUTION Keep the dummy cover for future use If a power supply unit is removed and not immediately replaced by a new one a dummy cover must be reinstalled in the bay to comply with applicable EMC regulations and satisfy cooling requirements ...

Page 108: ...r as it will go until the locking latch snaps in place 2 V CAUTION Ensure that the power supply unit properly engages in its slot and is locked in position in order to prevent it from sliding out of the chassis during transportation Ê If applicable fold down the handle on the power supply unit 6 3 1 4 Concluding steps Ê For the added power supply unit Connecting the server to the mains on page 67 ...

Page 109: ... stopper Ê Remove the CMA stopper with the mounted crossbar Ê Support the CMA stopper the crossbar and the CMA including cables with your right hand Ê Remove the power supply unit and install a dummy cover into the empty bay Ê Remount the complete assembly CMA stopper crossbar and CMA into the rail 6 3 2 1 Preliminary steps Ê Disconnect the power cord from the hot plug power supply unit see Discon...

Page 110: ...Fold up the handle on the power supply unit 1 Ê Press in on the green release latch 2 Ê While keeping the green release latch pressed pull the power supply unit out of its bay 3 V CAUTION Never leave the bay for the power supply unit empty for more than two minutes during operation Otherwise excessive temperatures could damage system components ...

Page 111: ...s bay until it locks in place V CAUTION Always install dummy covers into unused bays to comply with applicable EMC regulations and satisfy cooling requirements 6 3 3 Replacing a hot plug power supply unit V CAUTION When replacing a power supply unit in a non redundant PSU configuration the server must be switched off first Ensure to replace a defective power supply unit by a new one of the same ty...

Page 112: ...r crossbar and CMA into the rail 6 3 3 1 Preliminary steps Ê Locating the defective server on page 43 Ê Only when replacing a power supply unit in a non redundant configuration Shutting down the server on page 46 Ê Only when replacing a power supply unit in a non redundant configuration Disconnecting the server from the mains on page 46 6 3 3 2 Removing the defective hot plug power supply unit Ê I...

Page 113: ...eplacing a defective fan on page 96 6 3 4 Replacing the power distribution board 6 3 4 1 Preliminary steps Ê Locating the defective server on page 43 Ê Disabling BitLocker functionality on page 69 Ê Shutting down the server on page 46 Ê Disconnecting the server from the mains on page 46 Ê Getting access to the component on page 47 Ê Removing the fan module on page 151 6 3 4 2 Removing the hot plug...

Page 114: ...de and Maintenance Manual TX1330 M1 Power supply 6 3 4 3 Replacing the defective power distribution board Figure 38 Disconnecting power cables Ê Disconnect the two power cables from the power distribution board ...

Page 115: ...ower distribution board 3 Ê Insert the new power distribution board in the PSU cage 4 Ê Push the power distribution board in direction of the arrow 5 Ê Fasten the captive screw 6 Ê Connect the two power cables to the power distribution board see figure 38 6 3 4 4 Installing the hot plug power supply units Ê Install the power supply units as described in section Installing a hot plug power supply u...

Page 116: ...y one power supply unit for power supply redundancy the second power supply unit must be additionally ordered The upgrade kit for the redundant power supply consists of the following parts PSU cage with power distribution board incl power cables one hot plug power supply unit dummy cover if only one power supply unit is installed you have to install the dummy cover in the second bay several screws...

Page 117: ...d in section Removing the defective standard power supply unit on page 101 6 4 3 Installing the upgrade kit Figure 40 Installing the PSU cage Ê Insert the PSU cage into the chassis 1 Ê Slide the new PSU cage towards the rear of the chassis 2 Ê Secure the PSU cage with one screw 3 Ê Connect the two power cables to the power distribution board see figure 38 ...

Page 118: ...supply Figure 41 Securing the PSU cage Ê Secure the PSU cage to the chassis with five screws see circles Figure 42 Connecting power cables to the system board Ê Connect the black power connector to system board connector P30 1 see figure 203 on page 304 ...

Page 119: ...les Ê Install the power supply unit s as described in Installing a hot plug power supply unit on page 108 Ê If one bay remains empty install the dummy cover as described in Installing the dummy cover on page 111 6 4 4 Concluding steps Ê Installing the fan module on page 152 Ê Reassembling on page 58 Ê Connecting the server to the mains on page 67 Ê Switching on the server on page 68 Ê Enabling Bit...

Page 120: ...120 Upgrade and Maintenance Manual TX1330 M1 Power supply ...

Page 121: ... This does not indicate a failure Depending on the OS you can configure the write cache settings for the hard disk drives If a power failure should occur while the write cache is enabled cached data may be lost When disposing of transferring or returning a hard disk or solid state drive wipe out the data on the drive for your own security Rough handling of hard disk drives may damage the stored da...

Page 122: ...es solid state drives 7 1 Basic information Please refer to section 2 5 inch HDD SSD configurations on page 123 and section 3 5 inch HDD configurations on page 133 for a complete overview of the mounting sequences Install dummy modules into unused HDD SSD bays ...

Page 123: ...s SSDs Figure 43 2 5 inch HDD SSD mounting order example tower server 7 2 2 HDD SSD naming scheme I The HDD SSD numbering as listed in the ServerView RAID Manager differs from the HDD mounting order 2 5 inch HDDs SSDs Bay RAID Manager Channel log Drive Bay RAID Manager Channel log Drive 1 0 1 0 2 4 2 0 3 1 1 1 4 5 2 1 5 2 1 2 6 6 2 2 7 3 1 3 8 7 2 3 Table 4 HDD naming scheme ...

Page 124: ...ction 2 5 inch HDD SSD configurations on page 123 7 2 3 2 Removing a 2 5 inch HDD SSD dummy module Figure 44 Removing a 2 5 inch dummy module Ê Press both tabs together 1 and pull the dummy module out of its bay 2 V CAUTION Save the dummy module for future use Always replace dummy modules into unused HDD SSD bays to comply with applicable EMC regulations and satisfy cooling requirements Customer R...

Page 125: ...e Figure 45 Opening the 2 5 inch HDD SSD module locking lever Ê Pinch the green locking clips 1 and open the locking lever 2 Figure 46 Inserting the 2 5 inch HDD SSD module Ê Insert the HDD SSD module into a drive bay and carefully push back as far as it will go Ê Close the locking lever to lock the hard disk drive in place ...

Page 126: ...Replaceable Unit CRU Hardware 5 minutes Tools tool less RAID level Procedure RAID 0 Only remove an HDD module combined in a RAID 0 array if defective V CAUTION Removing an operational HDD module will result in data loss RAID 1 RAID 5 Removing an HDD module from a RAID 1 or RAID 5 array will not result in data loss However the removed drive needs to be replaced immediately by an HDD module of the s...

Page 127: ...mation please refer to the ServerView Suite RAID Management user guide Ê If applicable Removing the HDD bay cover on page 55 7 2 4 2 Removing a 2 5 inch HDD SSD module Figure 47 Removing a 2 5 inch HDD SSD module Ê Pinch the green locking clips and fully open the locking lever see figure 45 I Thereby the HDD SSD module is pushed out of its drive bay by about 1 cm and disconnected from the SAS SATA...

Page 128: ...ule is not replaced immediately always replace a dummy module into the unused HDD SSD bay to comply with applicable EMC regulations and satisfy cooling requirements Figure 48 Installing a 2 5 inch HDD SSD dummy module Ê Slide the HDD dummy module into the drive bay until it locks in place 7 2 4 4 Concluding steps Ê If applicable Installing the HDD bay cover on page 64 ...

Page 129: ...60 An HDD SSD module can only be replaced during operation in conjunction with a corresponding RAID configuration All HDD SSD modules drives must be uniquely identified so that they can be reinstalled in their original mounting locations later If this is not done existing data can be lost 7 2 5 1 Preliminary steps Ê Locating the defective server on page 43 Ê If applicable Removing the HDD bay cove...

Page 130: ... page 64 Ê Performing a RAID array rebuild on page 90 7 2 6 Replacing a 2 5 inch HDD SAS SATA backplane 7 2 6 1 Preliminary steps Ê Locating the defective server on page 43 Ê Disabling BitLocker functionality on page 69 Ê Shutting down the server on page 46 Ê Disconnecting the server from the mains on page 46 Ê Getting access to the component on page 47 Ê If applicable Removing the HDD bay cover o...

Page 131: ...D SAS SATA backplane Figure 49 Disconnecting cables Ê Disconnect the power cable 1 and the SAS SATA cable 2 from the desired SAS SATA backplane Ê Remove the two screws 3 see circles Figure 50 Removing the SAS SATA backplane Ê Lift up the SAS SATA backplane 1 and at a slight angle remove it from the guides on the HDD cage 2 ...

Page 132: ...the SAS SATA backplane with the two screws see figure 49 Ê Connect all cables to the SAS SATA backplane see figure 49 I For a complete cabling overview please refer to section Cabling plans on page 303 7 2 6 4 Concluding steps Ê Reassembling on page 58 Ê Reinstall all HDD SSD modules to their original drive bays as described in section Installing 2 5 inch HDD SSD modules on page 124 Ê Connecting t...

Page 133: ... configuration 4x 3 5 inch HDDs Figure 52 3 5 inch HDD mounting order example tower server 7 3 2 HDD naming scheme 7 3 3 Installing 3 5 inch HDD modules 3 5 inch HDDs Bay RAID Manager Channel log Drive Bay RAID Manager Channel log Drive 1 0 1 0 3 2 1 2 2 1 1 1 4 3 1 3 Table 5 HDD naming scheme Customer Replaceable Unit CRU Hardware 5 minutes ...

Page 134: ...the correct drive bay as described in section 3 5 inch HDD configurations on page 133 7 3 3 2 Removing a 3 5 inch HDD dummy module Figure 53 Removing a 3 5 inch dummy module Ê Press in on the locking tabs on both sides of the dummy module to disengage the locking mechanism 1 Ê While keeping the locking tabs pressed pull the dummy module out of its bay 2 Tools tool less ...

Page 135: ...odule for future use Always replace dummy modules into unused HDD bays to comply with applicable EMC regulations and satisfy cooling requirements 7 3 3 3 Installing a 3 5 inch HDD module Figure 54 Opening the 3 5 inch HDD module locking lever Ê While pressing down on the locking button 1 fold up the lever 2 ...

Page 136: ...ting the 3 5 inch HDD module Ê Insert the HDD module into a drive bay and carefully push back as far as it will go 1 Ê Fold down the lever to lock the HDD module in place 2 7 3 3 4 Concluding steps Ê If applicable Installing the HDD bay cover on page 64 Ê Performing a RAID array rebuild on page 90 ...

Page 137: ...e lost Be sure to back up your data before deleting a RAID array Customer Replaceable Unit CRU Hardware 5 minutes Tools tool less RAID level Procedure RAID 0 Only remove an HDD module combined in a RAID 0 array if defective V CAUTION Removing an operational HDD module will result in data loss RAID 1 RAID 5 Removing an HDD module from a RAID 1 or RAID 5 array will not result in data loss However th...

Page 138: ...HDD bay cover on page 55 7 3 4 2 Removing a 3 5 inch HDD module Figure 56 Removing a 3 5 inch HDD module Ê While pressing down on the locking button 1 fold up the lever 2 I Thereby the HDD module is pushed out of its drive bay by about 1 cm and disconnected from the SAS SATA backplane Ê Wait about 30 seconds to allow the hard disk drive to spin down Ê Pull the HDD module completely out of its bay ...

Page 139: ...odule is not replaced immediately always replace a dummy module into the unused HDD bay to comply with applicable EMC regulations and satisfy cooling requirements Figure 57 Installing a 3 5 inch HDD dummy module Ê Slide the dummy module into the drive bay until it locks in place 7 3 4 4 Concluding steps Ê If applicable Installing the HDD bay cover on page 64 ...

Page 140: ...g operation in conjunction with a corresponding RAID configuration All HDD modules drives must be uniquely identified so that they can be reinstalled in their original mounting locations later If this is not done existing data can be lost 7 3 5 1 Preliminary steps Ê Locating the defective server on page 43 Ê If applicable Removing the HDD bay cover on page 55 Ê Locate the defective HDD module as d...

Page 141: ...orming a RAID array rebuild on page 90 7 3 6 Replacing the 3 5 inch HDD SAS backplane 7 3 6 1 Preliminary steps Ê Locating the defective server on page 43 Ê Disabling BitLocker functionality on page 69 Ê Shutting down the server on page 46 Ê Disconnecting the server from the mains on page 46 Ê If applicable Removing the HDD bay cover on page 55 Ê Remove all HDD modules from the server as described...

Page 142: ...1 Hard disk drives solid state drives 7 3 6 2 Removing the defective 3 5 inch HDD SAS backplane Figure 58 Disconnecting cables Ê Disconnect the cables from the SAS backplane 1 power cable from connector x7 2 SAS SATA data cable from connector x1 ...

Page 143: ... inch HDD bay top cover see blue arrows Ê Remove one screw from the intrusion switch holder see orange arrow Figure 60 Removing the 3 5 inch HDD bay top cover B Ê Slide back the intrusion switch holder until it disengages from the HDD bay top cover 1 Ê Remove the intrusion switch holder 2 and set aside Ê Leave the intrusion switch cable connected to the system board ...

Page 144: ...ch HDD bay top cover C Ê Carefully fold up the 3 5 inch HDD bay top cover to disengage it from the SAS backplane below 1 Ê Remove the 3 5 inch HDD bay top cover from the chassis 2 Figure 62 Removing the 3 5 inch HDD SAS backplane Ê Pull up on the SAS backplane and remove it from the HDD bay in a vertical motion ...

Page 145: ...the new 3 5 inch HDD SAS backplane Figure 63 Installing the 3 5 inch HDD SAS backplane Ê Fit the SAS backplane into the guide on the outer wall of the HDD bay and lower it into the bottom rim see close up Ê Ensure that the SAS backplane is properly seated into the bottom rim and side guide see circles ...

Page 146: ...HDD bay top cover under the front chassis rim 1 Ê Fold down the HDD bay top cover 2 until it is properly seated on the HDD bays V CAUTION Ensure that the 3 5 inch HDD backplanes is properly secured in the upper rim of the HDD bay top cover Figure 65 Installing the 3 5 inch HDD bay top cover B Ê Place the intrusion switch holder on the HDD bay top cover as shown 1 ...

Page 147: ...rusion switch holder under the front chassis rim as far as it will go 2 Figure 66 Installing the 3 5 inch HDD bay top cover C Ê Secure the HDD bay top cover to the chassis with five screws see blue arrows Ê Secure the intrusion switch holder on the HDD bay top cover with one screw see orange arrow ...

Page 148: ...SAS backplane 1 power cable to connector x7 2 SAS SATA data cable to connector x1 7 3 6 5 Concluding steps Ê Reinstall all HDD modules to their original drive bays as described in section Installing 3 5 inch HDD modules on page 133 Ê Reassembling on page 58 Ê Connecting the server to the mains on page 67 Ê Switching on the server on page 68 Ê Enabling BitLocker functionality on page 90 ...

Page 149: ...ing internal options Circuit boards and soldered parts of internal options are exposed and can be damaged by static electricity Always discharge static build up e g by touching a grounded object before handling electrostatic sensitive devices ESDs Do not touch the circuitry on boards or soldered parts Hold circuit boards by their metallic areas or edges If devices are installed or disassembled usi...

Page 150: ...ned in an air duct directing airflow directly onto the CPU heat sink and memory slots I Additional fans in power supply units are integral parts of the power supply units and cannot be replaced separately V CAUTION Since the system fan is not redundant it has to be replaced immediately in case of defects or prefailure events 1 Air duct 2 System fan 120 x 38 mm ...

Page 151: ...hutting down the server on page 46 Ê Disconnecting the server from the mains on page 46 Ê Getting access to the component on page 47 8 2 2 Removing the fan module Figure 69 Removing the fan module Ê Disconnect the fan cable from system board connector FAN1 SYS 1 Upgrade and Repair Unit URU Hardware 5 minutes Tools tool less ...

Page 152: ...the fan module Figure 70 Installing the fan module Ê Lower the fan module into the chassis Ê Fit the four hooks on the fan module into the slots in the chassis see blue circles Ê Press down on the fan module until the four hooks lock in the narrow ends of the slots Ê Ensure that the locking tab on the fan module is properly engaged with the upper rim of the chassis see orange circle Ê Connect the ...

Page 153: ... Switching on the server on page 68 8 3 Replacing the system fan 8 3 1 Preliminary steps Ê Locating the defective server on page 43 Ê Shutting down the server on page 46 Ê Disconnecting the server from the mains on page 46 Ê Getting access to the component on page 47 Ê Removing the fan module on page 151 Upgrade and Repair Unit URU Hardware 5 minutes Tools tool less ...

Page 154: ...154 Upgrade and Maintenance Manual TX1330 M1 System fan and air duct 8 3 2 Removing the defective system fan Figure 71 Removing the fan cable from the guidings Ê Remove the fan cable from the guidings ...

Page 155: ...X1330 M1 Upgrade and Maintenance Manual 155 System fan and air duct Figure 72 Removing the safety pins from the snap rivets Ê Remove the safety pins see circles from the four snap rivets on the air duct ...

Page 156: ...Upgrade and Maintenance Manual TX1330 M1 System fan and air duct Figure 73 Removing the system fan from the air duct Ê Pull the system fan from the snap rivets 1 Ê Remove the system fan from the air duct 2 ...

Page 157: ...I Notice the position of the fan cable Ensure that the fan cable is not pressed Ê Insert and tightly push the four safety pins into the snap rivets 2 Ê Insert the fan cable in the guidings see figure 71 8 3 4 Concluding steps Ê Installing the fan module on page 152 Ê Reassembling on page 58 Ê Connecting the server to the mains on page 67 Ê Switching on the server on page 68 Ê Performing a fan test...

Page 158: ...158 Upgrade and Maintenance Manual TX1330 M1 System fan and air duct ...

Page 159: ...removing internal options Circuit boards and soldered parts of internal options are exposed and can be damaged by static electricity Always discharge static build up e g by touching a grounded object before handling electrostatic sensitive devices ESDs Do not touch the circuitry on boards or soldered parts Hold circuit boards by their metallic areas or edges If devices are installed or disassemble...

Page 160: ...n optional riser card This riser card can be mounted on two spacer bolts positioned under slot 1 In this case a PCI adapter board occupies slot 1 see section Installing the new riser card on page 185 PCI slot Type Function 1 PCe Gen2 x1 mechanical x4 slot for optional PCI adapter board connected with riser card 2 PCIe Gen 2 x4 mechanical x8 3 PCIe Gen3 x8 4 PCIe Gen3 x8 dedicated slot for boot con...

Page 161: ...Controller LSI SAS 2008 based 1 1 D2616 SAS RAID Controller LSI SAS 2108 based 1 1 D3116 SAS RAID Controller PCIe Gen 3 LSI SAS 2208 V3 based 1 1 D2627 PSAS CP200i Host Bus Adapter LSI SAS 2008 based 1 2 1 3 Ethernet controller Single Port Gigabit Desktop Adapter PRO 1000 CT 2 1 2 3 Single Port Gigabit Server Adapter PRO 1000 PF 2 1 2 3 Dual Port Gigabit Ethernet Controller D3035 2 1 2 3 Quad Port...

Page 162: ...llowing slot bracket for the ModularRAID controllers based on LSI MegaRAID Full height bracket not perforated Figure 76 Perforated and non perforated slot brackets Upgrade and Repair Unit URU Hardware 5 minutes Tools Phillips PH2 No 2 screw driver 1 Full height bracket non perforated 2 Full height bracket perforated 3 Low profile bracket perforated ...

Page 163: ...he PCI slot bracket A Ê Place the controller on the mounting tabs on the slot bracket Ê Carefully shift the slot bracket towards the controller until the plug shells engage with the cut outs in the slot bracket connector panel Figure 78 Installing the PCI slot bracket B Ê Secure the slot bracket to the controller with two screws ...

Page 164: ...abs on the slot bracket 1 Ê Carefully shift the slot bracket towards the controller until the plug shells engage with the cut outs in the slot bracket connector panel 2 Ê Ensure that the ESD springs on the plug shells properly engage with the slot bracket as shown see close ups Figure 80 Network adapter D2755 Mounting the slot bracket B Ê Secure the slot bracket to the controller with two M3 x 4 5...

Page 165: ...et C I Assembled network adapter D2755 Example network adapter D3035 Figure 82 Placing the slot bracket D3035 Ê Place the controller on the mounting tabs on the slot bracket 1 Ê Carefully shift the slot bracket towards the controller 2 until the plug shells engage with the cut outs in the slot bracket connector panel see close up 햲 햳 ...

Page 166: ...Maintenance Manual TX1330 M1 Expansion cards and backup units Figure 83 Fastening the slot bracket D3035 Ê Secure the slot bracket to the controller with two M3 x 4 5 mm screws Figure 84 Assembled network adapter D3035 ...

Page 167: ...g the slot bracket D3045 Ê Hinge the slot bracket to the plug shell as shown 1 Ê Fold the slot bracket towards the controller until the threaded mounting tab is aligned with the screw hole on the controller 2 Figure 86 Fastening the slot bracket D3045 Ê Secure the slot bracket to the controller with one M3 x 4 5 mm screw 햲 햳 ...

Page 168: ...its Figure 87 Assembled network adapter D3045 9 2 2 Removing a slot bracket Removing the slot bracket Ê Remove the two screws Ê Remove the controller from the mounting tabs on the slot bracket Upgrade and Repair Unit URU Hardware 5 minutes Tools Phillips PH2 No 2 screw driver ...

Page 169: ...odules Preparing the SFP transceiver module Figure 88 Removing the protective optical port plug Ê Remove the SFP transceiver module from its protective packaging Ê Remove the optical port plug from the new additional SFP transceiver module V CAUTION Always keep the protective port plugs attached to the transceiver optical bores and fiber optic cable connectors until you are ready to make a connect...

Page 170: ...tch and fold down the locking bail on the SFP transceiver module Inserting the SFP transceiver module Figure 90 Inserting the SFP transceiver module Ê Insert and slide the SFP transceiver module into the socket connector as far as it will go I If only one slot is equipped with a SFP transceiver module use the left connector as shown ...

Page 171: ...re 91 Latching the locking bail Ê Carefully fold up and latch the locking bail Figure 92 Attaching the protective optical port plug Ê If the SFP transceiver module is not immediately connected to an LC connector attach the protective optical port plug to the transceiver optical bores ...

Page 172: ...y SFP transceiver module Ê If applicable install the secondary SFP transceiver module accordingly 9 3 2 Removing an SFP transceiver module For Fiber Channel over Ethernet FCoE configurations the ethernet server adapter is equipped with one or two SFP small form factor pluggable transceiver modules Upgrade and Repair Unit URU Hardware 5 minutes Tools tool less ...

Page 173: ... port plug Ê If present remove the protective optical port plug from the SFP transceiver module V CAUTION Save the protective port plug for future use Figure 95 Unlatching the locking bail Ê Carefully unlatch and fold down the locking bail on the SFP transceiver module to eject the transceiver from the socket connector ...

Page 174: ...ts Figure 96 Removing the SFP transceiver Ê Pull the SFP transceiver module out of its socket connector Ê Reattach the protective optical port plug to the transceiver optical bores I Place the removed SFP transceiver module in an antistatic bag or other protective environment ...

Page 175: ...isabling BitLocker functionality on page 69 Ê Disabling SVOM boot watchdog functionality on page 70 Ê Shutting down the server on page 46 Ê Disconnecting the server from the mains on page 46 Ê Getting access to the component on page 47 Ê Removing the fan module on page 151 Upgrade and Repair Unit URU Hardware 5 minutes Software 5 minutes Tools Phillips PH2 No 2 screw driver ...

Page 176: ...Ê Fold up the locking handle on the slot bracket clamp 1 Ê Press down on the slot bracket clamp to disengage it 2 Ê Remove the slot bracket clamp 3 Ê Remove the slot bracket 4 V CAUTION Keep the slot bracket for further use Always replace slot brackets into unused PCI slot openings to comply with applicable EMC regulations and satisfy cooling requirements ...

Page 177: ... instructions regarding controller settings please refer to the accompanying documentation Ê If applicable attach the required slot bracket to the expansion card as described in section Installing a slot bracket on page 162 Figure 98 Installing the expansion card A Ê Carefully insert the expansion card into the desired PCI slot and press down firmly until it is fully seated in the slot ...

Page 178: ...expansion card see section Cabling plans on page 303 Ê If applicable install SFP transceiver modules to the expansion card as described in sections Installing SFP transceiver modules on page 169 Ê If applicable connect a BBU or FBU to the expansion card as described in sections Installing a BBU on page 197 or Installing an FBU on page 189 9 4 1 4 Concluding steps Ê Installing the fan module on pag...

Page 179: ...Enabling BitLocker functionality on page 90 Ê If applicable After replacing upgrading LAN controllers on page 94 9 4 2 Removing expansion cards 9 4 2 1 Preliminary steps Ê Disabling BitLocker functionality on page 69 Ê Shutting down the server on page 46 Ê Disconnecting the server from the mains on page 46 Ê Remove all external cables from the expansion card to be removed Ê Getting access to the c...

Page 180: ...card Ê If applicable remove SFP transceiver modules Removing an SFP transceiver module on page 172 Figure 100 Removing an expansion card Ê Fold up the locking handle on the slot bracket clamp 1 Ê Press down on the slot bracket clamp to disengage it 2 Ê Remove the slot bracket clamp 3 Ê Carefully pull up on the expansion card in a vertical motion and remove it from its slot 4 ...

Page 181: ...ents Figure 101 Installing a PCI slot bracket Ê Insert a PCI slot bracket into the unused PCI slot opening 1 Ê Clip on the PCI slot bracket clamp 2 Ê Fold down the locking handle on the PCI slot bracket clamp until it locks in place 3 9 4 2 4 Concluding steps Ê Installing the fan module on page 152 Ê Reassembling on page 58 Ê Connecting the server to the mains on page 67 Ê Switching on the server ...

Page 182: ...e Note on network settings recovery on page 182 Ê Disabling BitLocker functionality on page 69 Ê Disabling SVOM boot watchdog functionality on page 70 Ê Locating the defective server on page 43 Ê Shutting down the server on page 46 Ê Disconnecting the server from the mains on page 46 Ê Remove all external cables from the expansion card to be replaced Ê Getting access to the component on page 47 Ê ...

Page 183: ...tall the expansion card as described in section Installing expansion cards on page 175 Ê If applicable reinstall SFP transceiver modules on the expansion card as described in section Installing SFP transceiver modules on page 169 9 4 3 4 Concluding steps Ê Installing the fan module on page 152 Ê Reassembling on page 58 Ê Reconnect all external cables to the replaced expansion card Ê Connecting the...

Page 184: ...llers on page 94 9 4 4 Replacing the riser card 9 4 4 1 Preliminary steps Ê Locating the defective server on page 43 Ê Disabling BitLocker functionality on page 69 Ê Shutting down the server on page 46 Ê Disconnecting the server from the mains on page 46 Ê Remove all external cables from the expansion card installed in the riser card slot Ê Getting access to the component on page 47 Ê Removing the...

Page 185: ...s Figure 102 Removing the riser card Ê Disconnect the power cable 1 Ê Remove the two screws 2 Ê Remove the riser card 3 Ê Remove the PCI adapter board from slot 1 4 9 4 4 3 Installing the new riser card Figure 103 Preparing the riser card Ê Fold the cable under the riser card 1 ...

Page 186: ...ten the riser card with the two screws 3 Ê Connect the power cable 4 Ê Install the expansion card in the riser card slot as described in section Installing expansion cards on page 175 9 4 4 4 Concluding steps Ê Installing the fan module on page 152 Ê Reassembling on page 58 Ê Reconnect all external cables to the expansion card installed in the riser card slot Ê Connecting the server to the mains o...

Page 187: ...n page 46 Ê Remove all external cables from the expansion card to be removed Ê Getting access to the component on page 47 Ê Removing the fan module on page 151 9 4 5 2 Removing the defective TFM Ê Remove the depending expansion card as described in section Removing an expansion card on page 180 Ê Disconnect the FBU adapter cable as described in section Disconnecting the FBU adapter cable from the ...

Page 188: ...on page 191 Ê Connect the FBU adapter cable to the TFM as described in section Connecting the FBU adapter cable to the TFM on page 196 Ê Install the expansion card as described in section Installing expansion cards on page 175 9 4 5 4 Concluding steps Ê Installing the fan module on page 152 Ê Reassembling on page 58 Ê Reconnect all external cables to the replaced expansion card Ê Connecting the se...

Page 189: ... to two backup units 9 5 2 Installing an FBU V CAUTION For further safety information please refer to chapter Important information on page 31 9 5 2 1 Preliminary steps Ê Disabling SVOM boot watchdog functionality on page 70 Ê Shutting down the server on page 46 Ê Disconnecting the server from the mains on page 46 Ê Getting access to the component on page 47 Ê Removing the fan module on page 151 U...

Page 190: ...s and backup units 9 5 2 2 Installing TFM to the RAID controller if applicable Figure 106 TFM kit Figure 107 Installing TFM Ê Fit the spacer bolts of the TFM on the RAID controller 1 Ê Secure the TFM on the RAID controller with the three screws 2 1 TFM 2 Screws ...

Page 191: ...1 Expansion cards and backup units 9 5 2 3 Installing the FBU in the holder Figure 108 Installing the FBU in the holder A Ê At a slight angle fit the FBU under the right retaining bracket on the holder Ê Push down the FBU until it locks in place ...

Page 192: ...192 Upgrade and Maintenance Manual TX1330 M1 Expansion cards and backup units Figure 109 Installing the FBU in the holder B Ê Ensure that the FBU is properly seated in the holder ...

Page 193: ...TX1330 M1 Upgrade and Maintenance Manual 193 Expansion cards and backup units Figure 110 Connecting the FBU adapter cable to the FBU Ê Connect the cable end on the FBU to the FBU adapter cable ...

Page 194: ...o the chassis Figure 111 Installing the FBU holder A I Note the positions of the fixation bolts on the chassis floor and keyhole slots on the FBU holder Ê Insert the FBU holder into the chassis so that the three fixation bolts on the chassis floor rest in the wide ends of the keyhole slots on the holder FBU 1 FBU 2 ...

Page 195: ...gure 112 Installing the FBU holder B Ê Slide the FBU holder downward as far as it will go The fixation bolts on the chassis floor will lock in the narrow ends of the keyhole slots on the holder Ê Ensure that the locking handle on the FBU holder properly snaps in place see close up ...

Page 196: ... cable Ê Connect the FBU adapter cable to the TFM Ê Route the FBU adapter cable as shown 9 5 2 6 Concluding steps Ê Installing the fan module on page 152 Ê Reassembling on page 58 Ê Connecting the server to the mains on page 67 Ê Switching on the server on page 68 Ê Updating RAID controller firmware on page 80 Ê Enabling SVOM boot watchdog functionality on page 84 ...

Page 197: ...ary steps Ê Disabling SVOM boot watchdog functionality on page 70 Ê Shutting down the server on page 46 Ê Disconnecting the server from the mains on page 46 Ê Getting access to the component on page 47 Ê Removing the fan module on page 151 9 5 3 2 Connecting the BBU cable to the BBU Figure 114 Connecting the BBU cable Ê Connect the BBU cable to the BBU Upgrade and Repair Unit URU Hardware 5 minute...

Page 198: ...a slight angle fit the BBU under the right retaining bracket on the BBU holder 1 Ê Fold down the BBU until it locks in place 2 9 5 3 4 Installing the BBU holder into the chassis Ê Install the BBU holder into the chassis as described in section Installing the FBU holder into the chassis on page 194 9 5 3 5 Connecting the BBU cable to a controller Ê If applicable install a RAID controller as describ...

Page 199: ...er In this case the BBU will automatically enter a trickle charge cycle for recovery This initial charge may take up to 8 hours before the BBU will initiate a recalibration cycle Ê Enter the ServerView RAID Manager and check the current BBU status I For further information please refer to the ServerView Suite RAID Management user guide Ê If the BBU is shown as bad or defective do not power off the...

Page 200: ...efer to section Environmental protection on page 41 9 5 4 1 Preliminary steps Ê Shutting down the server on page 46 Ê Disconnecting the server from the mains on page 46 Ê Getting access to the component on page 47 Ê Removing the fan module on page 151 9 5 4 2 Disconnecting the FBU adapter cable from the TFM Figure 116 Disconnecting the FBU adapter cable from the TFM Ê Disconnect the FBU adapter ca...

Page 201: ...e on the FBU holder 1 while sliding the BBU holder upward as far as it will go 2 I After that the fixation bolts on the chassis floor will rest in the wide ends of the keyhole slots on the holder Ê Lift the FBU holder out of the chassis 3 9 5 4 4 Concluding steps Ê Installing the fan module on page 152 Ê Reassembling on page 58 Ê Connecting the server to the mains on page 67 Ê Switching on the ser...

Page 202: ...er from the mains on page 46 Ê Getting access to the component on page 47 Ê Removing the fan module on page 151 9 5 5 2 Disconnecting the BBU cable from the controller Ê Carefully disconnect the BBU cable from the RAID controller 9 5 5 3 Removing the BBU holder from the chassis Ê Remove the BBU holder from the chassis as described in section Removing the FBU holder from the chassis on page 201 9 5...

Page 203: ...al protection on page 41 9 5 6 1 Preliminary steps Ê Locating the defective server on page 43 Ê Disabling SVOM boot watchdog functionality on page 70 Ê Shutting down the server on page 46 Ê Disconnecting the server from the mains on page 46 Ê Getting access to the component on page 47 Ê Removing the fan module on page 151 9 5 6 2 Removing the defective FBU Ê Remove the FBU with the holder as descr...

Page 204: ...intenance Manual TX1330 M1 Expansion cards and backup units Figure 118 Disconnecting the FBU adapter cable from the FBU Ê Press down on the locking latch on the FBU cable see close up and disconnect the FBU adapter cable ...

Page 205: ...nd remove it 9 5 6 3 Installing the new FBU Ê Install the FBU as described in section Installing an FBU on page 189 9 5 6 4 Concluding steps Ê Installing the fan module on page 152 Ê Reassembling on page 58 Ê Connecting the server to the mains on page 67 Ê Switching on the server on page 68 Ê If applicable Updating RAID controller firmware on page 80 Ê Enabling SVOM boot watchdog functionality on ...

Page 206: ...ironmental protection on page 41 9 5 7 1 Preliminary steps Ê Locating the defective server on page 43 Ê Disabling SVOM boot watchdog functionality on page 70 Ê Shutting down the server on page 46 Ê Disconnecting the server from the mains on page 46 Ê Getting access to the component on page 47 Ê Removing the fan module on page 151 9 5 7 2 Removing the defective BBU Ê Remove the BBU with the holder ...

Page 207: ...he BBU holder Ê Press out on the right retaining bracket on the BBU holder to disengage the locking mechanism while pulling up on the BBU 1 Ê Fold up the BBU and at a slight angle remove it from the BBU holder 2 Figure 121 Disconnecting the BBU cable from the BBU Ê Carefully disconnect the BBU cable from the BBU ...

Page 208: ...ow as bad or defective in the ServerView RAID Manager In this case the BBU will automatically enter a trickle charge cycle for recovery This initial charge may take up to 8 hours before the BBU will initiate a recalibration cycle Ê Enter the ServerView RAID Manager and check the current BBU status I For further information please refer to the ServerView Suite RAID Management user guide Ê If the BB...

Page 209: ...atedly Doing so may cause failures Pressing out the securing clips on the memory module connector will eject the installed memory module To prevent damage and injuries eject memory modules carefully without applying excessive force For further information please refer to chapter Important information on page 31 10 1 Basic information The system board is equipped with four memory slots The system h...

Page 210: ...memory modules with different capacities are used Install modules with higher capacities first Within a channel install modules in descending order of capacity If memory modules with different speeds are used the lowest clock rate applies for all DIMMs Figure 122 Memory overview Channel A B Slot ID 1A 2A 1B 2B DIMM 1 o 2 o o 3 o o o 4 o o o o Table 6 Mounting order Mirrored Channel Mode Single CPU...

Page 211: ...e Regardless of the mode all DIMMs will run at the highest common frequency that is allowed by the SPD Data of the DIMMs and the maximum speed of the selected configuration Single channel mode is used if one memory module is populated in DIMM 1A 10 2 Removing memory modules 10 2 1 Preliminary steps Ê Disabling BitLocker functionality on page 69 Ê Disabling SVOM boot watchdog functionality on page ...

Page 212: ...9 Figure 123 Removing memory modules Ê Eject the desired memory module by pressing out the securing clips at each end of the memory slot 1 Ê Remove the ejected memory module 2 10 2 3 Concluding steps Ê Installing the fan module on page 152 Ê Reassembling on page 58 Ê Connecting the server to the mains on page 67 Ê Switching on the server on page 68 Ê If applicable Updating or recovering the system...

Page 213: ...n the server on page 46 Ê Disconnecting the server from the mains on page 46 Ê Getting access to the component on page 47 Ê Removing the fan module on page 151 10 3 2 Installing a memory module Ê Identify the correct memory slot see section Memory sequence on page 210 Figure 124 Installing memory modules Ê Press out the securing clip at each end of the memory slot 1 Upgrade and Repair Unit URU Har...

Page 214: ... Ê If applicable Updating or recovering the system board BIOS and iRMC on page 76 Ê Enabling SVOM boot watchdog functionality on page 84 Ê If applicable Verifying the memory mode on page 85 Ê Enabling BitLocker functionality on page 90 10 4 Replacing memory modules 10 4 1 Preliminary steps Ê Identify the defective memory slot using the server management software Ê Disabling BitLocker functionality...

Page 215: ...emoving a memory module on page 212 10 4 3 Installing the new memory module Ê Install the memory module as described in section Installing a memory module on page 213 10 4 4 Concluding steps Ê Installing the fan module on page 152 Ê Reassembling on page 58 Ê Connecting the server to the mains on page 67 Ê Switching on the server on page 68 Ê If applicable Updating or recovering the system board BI...

Page 216: ...216 Upgrade and Maintenance Manual TX1330 M1 Main memory ...

Page 217: ...d up e g by touching a grounded object before handling electrostatic sensitive devices ESDs Do not touch the circuitry on boards or soldered parts Hold circuit boards by their metallic areas or edges When removing or installing the processor be careful not to touch or bend the spring contacts on the processor socket Never touch the underside of the processor Even minor soiling such as grease from ...

Page 218: ...om its protective sleeve or from its socket place it upside down on a nonconducting antistatic surface Never push a processor over a surface 11 2 1 Preliminary steps Ê Disabling BitLocker functionality on page 69 Ê Disabling SVOM boot watchdog functionality on page 70 Ê If applicable Locating the defective server on page 43 Ê Shutting down the server on page 46 Ê Disconnecting the server from the ...

Page 219: ...e heat sink back and forth to detach it from the processor This may be necessary due to the adhesive quality of the thermal paste located between the heat sink and processor V CAUTION Pay special attention not to damage any system board components surrounding the processor socket Ê Lift the heat sink out of the chassis Ê Thoroughly clean residual thermal paste from the surface of the heat sink and...

Page 220: ...g the processor Figure 126 Unlatching the socket lever Ê Unlatch the socket lever by pushing it down and away from the socket 1 Ê Fold back the socket release lever 2 Figure 127 Removing the processor Ê Rotate the socket lever to lift the load plate away from the socket 1 ...

Page 221: ...or Ê Hold the processor with your thumb and index finger Make sure that the notches on the processor align with the posts on the socket see circles Ê Lower the processor straight down without tilting or sliding it in the socket V CAUTION Ensure that the processor is level in the socket Be careful not to touch or bend the pins on the processor socket Never touch the underside of the processor Even ...

Page 222: ...te A Ê Lower the load plate over the processor while leaving the socket lever in the open position Figure 130 Closing the load plate B Ê Lower the socket lever while making sure that the front edge of the load plate slides under the shoulder screw cap see close up as the lever is lowered ...

Page 223: ...ng thermal paste I For the Japanese market the service engineer must follow the instruction provided separately I If the processor upgrade or replacement kit contains a new CPU heat sink a thin layer of thermal compound has already been pre applied to its lower surface In this case please proceed with section Installing the processor heat sink on page 225 ...

Page 224: ... syringe FTS FSP P304000004 contains thermal paste for three processors In order to determine the correct amount of thermal paste equal to 1 0 gram divide the grey area of the syringe up into three equal segments I Add graduation marks to the syringe using a permanent marker to help you apply the thermal paste ...

Page 225: ...t shaped amount of thermal paste 1 0 gram see description above to the center of the processor surface as shown V CAUTION Do not mix different types of thermal paste 11 2 6 Installing the processor heat sink Figure 134 Installing the heat sink A Ê Carefully seat the heat sink on the four threaded holes as shown ...

Page 226: ...eat sink are properly seated on the threaded holes Ensure that the heat sink cooling fins match the direction of the airflow Figure 135 Installing the heat sink B Ê Fasten the four captive screws on the heat sink in a crossover pattern screw torque 0 6 Nm not applicable for the Japanese market 1 4 ...

Page 227: ...r functionality on page 90 11 3 Replacing the processor heat sink 11 3 1 Preliminary steps Ê Locating the defective server on page 43 Ê Shutting down the server on page 46 Ê Getting access to the component on page 47 Ê Removing the fan module on page 151 11 3 2 Replacing the processor heat sink Ê Remove the processor heat sink as described in section Removing the processor heat sink on page 219 Ê ...

Page 228: ...he processor heat sink as described in section Installing the processor heat sink on page 225 11 3 3 Concluding steps Ê Installing the fan module on page 152 Ê Reassembling on page 58 Ê Connecting the server to the mains on page 67 Ê Switching on the server on page 68 ...

Page 229: ...he casing may cause failures When disposing of transferring or returning a backup drive ensure that all backup media has been removed from the drive Do not touch the circuitry on boards or soldered parts Hold circuit boards by their metallic areas or edges Circuit boards and soldered parts of internal options are exposed and can be damaged by static electricity Always discharge static build up e g...

Page 230: ...ounting order for accessible drives The server offers three 5 25 inch accessible drive bays for optical disk drives and backup drives Figure 136 Accessible drives mounting order tower server Figure 137 Accessible drives mounting order rack server 5 25 inch x 1 6 inch 5 25 inch x 1 6 inch ...

Page 231: ...ving the front cover on page 56 tower server I The front cover only needs to be removed in order to remove or install accessible drive dummy covers Sequence Accessible drive Bay Max no 1 Optical disk drive or slimline optical disk drive Bay 1 1 2 Backup drive LTOx Bay 3 if occupied bay 2 or bay 1 1 3 Backup drive DAT Bay 3 if occupied bay 2 or bay 1 2 4 Backup drive RDX Bay 3 if occupied bay 2 or ...

Page 232: ...e drive filler covers Figure 138 Removing an accessible drive filler cover Ê Hold the accessible drive filler cover by its two handle recesses and pull it out of the desired installation bays V CAUTION Always replace filler covers into unused drive bays to comply with applicable EMC regulations and satisfy cooling requirements ...

Page 233: ... accessible drive covers I Removing accessible drive covers is illustrated by the example of the tower server In case of the rack front cover the procedure is identical Ê Turn the front cover face down Ê Press in on the lugs on either side of the drive cover Ê Fold up 1 and remove the desired accessible drive covers 2 ...

Page 234: ...rately with the backup drive I No new mounting brackets are available when replacing a backup drive during service Ê If applicable remove existing mounting brackets from the backup drive Figure 140 Backup drive mounting brackets Figure 141 Screw holes on backup drive mounting brackets Ê Note the screw hole description stamped onto the mounting bracket Ê Use the square screw hole for RDX backup dri...

Page 235: ...ts to an RDX backup drive Ê Secure the backup drive mounting brackets to the RDX backup drive with two screws per bracket as shown Figure 143 Securing mounting brackets to a DAT72 backup drive Ê Secure the backup drive mounting brackets to the DAT72 backup drive with two screws per bracket as shown ...

Page 236: ...ide in unit for slimline ODD Figure 145 Mounting the slimline ODD in the slide in unit Ê Insert the slimline ODD on the top Ê Fasten it with one M2 x 2 5 mm screw to the slide in unit on the right side Ê Fasten it with two M2 x 2 5 mm screws to the slide in unit on the left side Ê Install the slide in unit as described in section Installing an accessible drive ...

Page 237: ...sible drive locking bar 2 I Unlocking and securing the front panel and accessible drives is illustrated by the example of tower servers In case of rack servers the accessible drive locking bar is located on the side of the drive bay In this case proceed as follows Figure 147 Opening the accessible drive locking bar rack systems Ê Pull up on the locking latch to disengage the accessible drive locki...

Page 238: ...ront screw hole on the front panel frame lines up with the centering pin on the locking bar 1 V CAUTION For installing a LTO drive ensure that the power cables routed behind the accessible drive cage are not trapped when pushing the LTO drive in its bay Ê Close the locking bar 2 until it locks in place 3 Ê Connect the cables according to your configuration see section Cabling plans on page 303 ...

Page 239: ... 1 Cabling of RDX drive Figure 149 Cabling of RDX backup drive Ê Connect the connector on the RDX drive to the USB 3 0 cable of the front panel 1 Ê Connect the connector P1 to system board connector SATA POWER 2 Ê Run the cables through the cable guide as shown see arrow ...

Page 240: ...USB 3 0 RDX drive may be connected with a USB 2 0 cable to the onboard USB 2 0 connector with limited performance The USB 3 0 cable cannot be connected to a USB 2 0 RDX drive 12 2 6 Concluding steps Ê Installing the rack front cover on page 58 rack server or Installing the front cover on page 63 tower server Ê Reassembling on page 58 Ê Connecting the server to the mains on page 67 Ê Switching on t...

Page 241: ...Ê Getting access to the component on page 47 Ê Removing the rack front cover on page 52 rack server or Removing the front cover on page 56 tower server I The front cover only needs to be removed in order to remove or install accessible drive dummy covers 12 3 2 Removing an accessible drive Ê Disconnect all cables from the accessible drive Ê Press out on the locking latch to disengage the accessibl...

Page 242: ... and Maintenance Manual TX1330 M1 Accessible drives Figure 151 Removing the accessible drive Ê Carefully pull the accessible drive out of its installation bay 1 Ê Close the locking bar 2 until it locks in place 3 ...

Page 243: ...s Figure 152 Installing an accessible drive filler cover Ê Hold the accessible drive filler cover by its two handle recesses and insert it into the empty installation bays with the punched out arrow symbol facing up V CAUTION Always replace filler covers into unused drive bays to comply with applicable EMC regulations and satisfy cooling requirements ...

Page 244: ...e drive filler cover has been installed in every empty drive bay Ê Turn the front cover face down Ê Join the two lugs on one edge of the accessible drive cover with the right inner edge of the front cover 1 Ê Fold down the accessible drive cover until it snaps in place 2 12 3 4 Concluding steps Ê Installing the rack front cover on page 58 rack server or Installing the front cover on page 63 tower ...

Page 245: ...hutting down the server on page 46 Ê Disconnecting the server from the mains on page 46 Ê Getting access to the component on page 47 Ê Removing the rack front cover on page 52 rack server or Removing the front cover on page 56 tower server I Removing the front cover is not required in order to replace an accessible drive 12 4 2 Removing the defective accessible drive Ê Remove the accessible drive ...

Page 246: ...n section Installing an accessible drive on page 237 12 4 4 Concluding steps Ê Installing the rack front cover on page 58 rack server or Installing the front cover on page 63 tower server Ê Reassembling on page 58 Ê Connecting the server to the mains on page 67 Ê Switching on the server on page 68 Ê If applicable Verifying and configuring the backup software solution on page 81 Ê Enabling BitLocke...

Page 247: ...oards and soldered parts of internal options are exposed and can be damaged by static electricity Always discharge static build up e g by touching a grounded object before handling electrostatic sensitive devices ESDs Do not touch the circuitry on boards or soldered parts Hold circuit boards by their metallic areas or edges For further information please refer to chapter Important information on p...

Page 248: ... board to the new system board V CAUTION For that reason the front panel module and system board must not be replaced simultaneously In this case restoring the system configuration data on the system board would fail 13 1 1 Preliminary steps Ê Disabling BitLocker functionality on page 69 Ê Disabling SVOM boot watchdog functionality on page 70 Ê Locating the defective server on page 43 Ê Shutting d...

Page 249: ...moving the fan module on page 151 13 1 2 Removing the defective front panel module Figure 154 Disconnecting cables from system board Ê Disconnect the front panel cable 1 and the front USB cable 2 from the system board Ê Remove both cables from the cable clamp see circle ...

Page 250: ...panel module Ê Press out on the locking latch to disengage the accessible drive locking bar 1 Ê Fold up the accessible drive locking bar 2 Ê Carefully pull the front panel module out of its bay 3 V CAUTION Ensure that none of the cables are strained or damaged Figure 156 Removing the cable clamp ...

Page 251: ...nt panel cable from the front panel module 13 1 3 Installing the new front panel module Ê Connect the front panel cable to the front panel module see figure 157 Figure 158 Installing the front panel module Ê Insert the front panel module into its installation bay and carefully push in until the front screw hole on the front panel frame lines up with the centering pin on the locking bar 1 ...

Page 252: ... rack server or Installing the front cover on page 63 tower server Ê Reassembling on page 58 Ê Connecting the server to the mains on page 67 Ê Switching on the server on page 68 Ê Verifying system information backup restore on page 79 Ê Store your server s system information on the Chassis ID EPROM integrated into the front panel board For further information on how to obtain and use the ChassisId...

Page 253: ...For further information please refer to chapter Important information on page 31 14 1 Basic information This section provides instructions for the system board and the following components CMOS battery CMOS memory volatile BIOS memory and the real time clock are powered by a lithium coin cell CMOS battery This cell lasts up to ten years depending on ambient temperature and use If the CMOS battery ...

Page 254: ... disposed of in accordance with local regulations concerning special waste For further safety information please refer to section Environmental protection in the operating manual of your server Ensure to insert the CMOS battery the with the positive pole facing up 14 2 1 Preliminary steps Ê Locating the defective server on page 43 Ê Shutting down the server on page 46 Ê Disconnecting the server fr...

Page 255: ...oothpick recommended or similar tool as a lever Insert the toothpick between the battery and locking spring as shown 2 V CAUTION Do not use sharp edged tools like screw drivers as they may damage system board components when slipping Ê Carefully pry the depleted CMOS battery out of its socket as shown 3 Ê Remove the CMOS battery 4 I Do not throw the CMOS battery into the trash can Lithium batterie...

Page 256: ...g up as shown see close up Ê Fold down the CMOS battery 2 until it locks in place Ê Ensure that the locking spring 3 is properly engaged 14 2 3 Concluding steps Ê Dispose of the CMOS battery in accordance with local regulations concerning special waste Ê Reassembling on page 58 Ê Connecting the server to the mains on page 67 Ê Verifying system information backup restore on page 79 Ê Verifying the ...

Page 257: ...ing SVOM boot watchdog functionality on page 70 Ê Locating the defective server on page 43 Ê Shutting down the server on page 46 Ê Disconnecting the server from the mains on page 46 Ê Getting access to the component on page 47 14 3 1 2 Installing the UFM Figure 161 UFM kit Field Replaceable Unit FRU Hardware 5 minutes Software 5 minutes Tools tool less 1 USB Flash Module UFM 2 UFM spacer 3 UFM nyl...

Page 258: ...nstalling the UFM Ê Connect the UFM to the system board snapping in the UFM spacer 14 3 1 3 Concluding steps Ê Reassembling on page 58 Ê Connecting the server to the mains on page 67 Ê Switching on the server on page 68 Ê Enabling SVOM boot watchdog functionality on page 84 Ê Enabling BitLocker functionality on page 90 ...

Page 259: ...D into the DVD drive and close the drive tray Ê The server should now boot from the Recovery Tool CD Ê Follow the on screen instructions 14 3 2 Removing the UFM 14 3 2 1 Preliminary steps Ê Disabling BitLocker functionality on page 69 Ê Locating the defective server on page 43 Ê Shutting down the server on page 46 Ê Disconnecting the server from the mains on page 46 Ê Getting access to the compone...

Page 260: ...UFM A Ê Remove the nylon screw 1 Ê Disconnect and remove the UFM 2 Figure 165 Removing the UFM B Ê The UFM spacer remains on the system board 14 3 2 3 Concluding steps Ê Reassembling on page 58 Ê Connecting the server to the mains on page 67 Ê Switching on the server on page 68 Ê Enabling BitLocker functionality on page 90 ...

Page 261: ...on page 43 Ê Shutting down the server on page 46 Ê Disconnecting the server from the mains on page 46 Ê Getting access to the component on page 47 14 3 3 2 Removing the defective UFM Ê Remove the UFM from the system board as described in section Removing the UFM on page 259 Ê The UFM spacer remains on the system board Field Replaceable Unit FRU Hardware 10 minutes Software 5 minutes Tools Phillips...

Page 262: ...3 Installing the new UFM Figure 166 Preparing the new UFM Ê Remove the nylon screw from the new UFM 1 Ê Remove the UFM spacer 2 Figure 167 Installing the UFM Ê Fit the UFM on the UFM connector and the remaining UFM spacer 1 Ê Secure the UFM to the UFM spacer with the nylon screw 2 ...

Page 263: ...er If the customer requests disposal of the defective UFM proceed as follows Figure 168 Destroying the defective UFM Ê Use a pair of combination pliers 1 and flat nose pliers 2 to break the UFM in half as shown 14 3 3 4 Concluding steps Ê Reassembling on page 58 Ê Connecting the server to the mains on page 67 Ê Switching on the server on page 68 Ê Enabling SVOM boot watchdog functionality on page ...

Page 264: ...ecovery Tool CD Ê Follow the on screen instructions 14 4 Trusted Platform Module TPM 14 4 1 Installing the TPM 14 4 1 1 Preliminary steps Ê Disabling BitLocker functionality on page 69 Ê Locating the defective server on page 43 Ê Shutting down the server on page 46 Ê Disconnecting the server from the mains on page 46 Ê Getting access to the component on page 47 Field Replaceable Unit FRU Hardware ...

Page 265: ...Figure 169 TPM kit Figure 170 TPM mounting location Figure 171 Installing the TPM spacer Ê Snap the TPM spacer into the cut out in the system board 1 TPM Trusted Platform Module 3 Special screw for TPM 2 TPM spacer I The black TPM spacer is not used in this server 4 TPM bit insert for TPM special screw ...

Page 266: ...Manual TX1330 M1 System board and components Figure 172 Installing the TPM Ê Connect the TPM to the system board Figure 173 TPM bit insert Ê Attach the TPM bit insert or TPM module fixing tool Japanese market to a bit screw driver ...

Page 267: ... page 68 Ê Enable TPM in the system board BIOS Proceed as follows Ê Switch on or restart your server Ê As soon as the startup screen appears press the F2 function key to enter the BIOS Ê Select the Advanced menu Ê Select the Trusted Computing submenu Ê Set the TPM Support and TPM State settings to Enabled Ê Under Pending TPM operation select the desired TPM operation mode Ê Save your changes and e...

Page 268: ...reliminary steps Ê Before removing the TPM it is necessary to remove BitLocker protection from the computer and to decrypt the volume Ask the system administrator to turn off BitLocker protection using the BitLocker setup wizard available either from the Control Panel or Windows Explorer Ê Open Bitlocker Drive Encryption by clicking the Start button clicking Control Panel clicking Security and the...

Page 269: ...net web pages Ê Disable TPM in the system board BIOS Proceed as follows Ê Switch on or restart your server Ê As soon as the startup screen appears press the F2 function key to enter the BIOS Ê Select the Advanced menu Ê Select the Trusted Computing submenu Ê Set the TPM Support and TPM State settings to Disabled Ê Save your changes and exit the BIOS I For more information on how to access the BIOS...

Page 270: ... s screw driver or the dedicated TPM screw driver Japanese market 2 V CAUTION Ensure to turn the screw clockwise in order to remove it Slowly and carefully increase the pressure on the screw until it begins to turn The effort when loosing the screw should be as low as possible Otherwise the thin metal bar may break rendering it impossible to loosen the screw Ê Remove the TPM screw 3 Ê Remove the T...

Page 271: ...of combination pliers press together the hooks on the TPM spacer 1 see close up and remove it from the system board 2 I If the TPM is to be replaced the TPM spacer may remain on the system board 14 4 2 3 Concluding steps Ê Reassembling on page 58 Ê Connecting the server to the mains on page 67 Ê Switching on the server on page 68 ...

Page 272: ... TPM will cause to lose all data 14 4 3 1 Preliminary steps Ê Disabling BitLocker functionality on page 69 Ê Locating the defective server on page 43 Ê Shutting down the server on page 46 Ê Disconnecting the server from the mains on page 46 Ê Getting access to the component on page 47 Ê Removing the fan module on page 151 Field Replaceable Unit FRU Hardware 40 minutes Tools Removing the system boa...

Page 273: ...ard when removing the defective TPM 14 4 3 3 Installing the new TPM Ê The TPM spacer is already present on the system board Ê Install the TPM as described in section Installing the TPM on page 264 14 4 3 4 Concluding steps Ê Installing the fan module on page 152 Ê Reassembling on page 58 Ê Connecting the server to the mains on page 67 Ê Switching on the server on page 68 Ê Enabling BitLocker funct...

Page 274: ...description please refer to section Replacing the TPM on page 272 The TPM is activated in the system BIOS V CAUTION Before replacing the system board ask the customer whether TPM functionality is used Field Replaceable Unit FRU Hardware 50 minutes Software 10 minutes Tools Replacing the system board Phillips PH2 No 2 screw driver Magnifying glass for inspecting processor socket springs recommended...

Page 275: ...ckup copy of important system configuration data is automatically stored from the system board NVRAM to the Chassis ID EPROM After replacing the system board the backup data is restored from the Chassis ID board to the new system board V CAUTION For that reason the front panel module and system board must not be replaced simultaneously In this case restoring the system configuration data on the sy...

Page 276: ...board Ê Remove all cables from the system board Ê Remove the following components from the system board Heat sink see section Removing the processor heat sink on page 219 I Leave the processor on the defective board for now Memory modules refer to section Removing memory modules on page 211 I Ensure to take note of the memory modules mounting positions for reassembly Expansion cards refer to the s...

Page 277: ...mponents Figure 177 Screws system board Ê Remove eight screws from the system board see circles Figure 178 Detaching the system board Ê Slightly lift up the system board by the memory module ejectors and a PCI slot 1 in order to detach it from the centering bolts C ...

Page 278: ...shells disengage from the cut outs in the connector panel 2 Figure 179 Removing the system board Ê Hold the defective system board by the memory module ejectors and a PCI slot and at a slight angle lift it out of the chassis Ê If applicable remove the TPM as described in section Removing the TPM on page 269 Figure 180 Removing the power cable clamp ...

Page 279: ...5 3 Installing the new system board Figure 181 Installing the system board A Ê Hold the system board by the memory module ejectors and a PCI slot V CAUTION Do not lift or handle the system board by any of its heat sinks Ensure not to damage the EMI springs to comply with applicable EMC regulations and satisfy cooling requirements and fire protection measures Ê At a slight angle lower the system bo...

Page 280: ...ector panel Ê Lower the system board onto the centering bolts C Ensure that the system board is properly seated on both centering bolts Ê Secure the system board with eight screws see circles in figure 177 on page 277 I Screw torque 0 6 Nm not applicable for the Japanese market Tighten the screws in a cross diagonal pattern Figure 183 Installing the power cable clamp Ê Press down on the power cabl...

Page 281: ... 333 14 5 4 Swapping the processor Figure 184 Unlatching the socket lever new system board Ê Unlatch the socket lever on the new system board by pushing it down and away from the socket 1 Ê Fold back the socket lever to disengage the load plate 2 Ê Rotate the socket lever to lift the load plate Ê Make sure that the load plate is in the fully open position ...

Page 282: ... Save the socket cover for future use Always replace the socket cover if you remove the processor from the socket Ê Use a magnifying glass recommended to inspect the socket spring contacts for damages from different angles Do not use the spare system board if any irregularities are visible Possible damages Contact spring is bent backwards upon itself Contact spring tip position is shifted or out o...

Page 283: ...1 Figure 186 Installing the protective socket cover defective system board A I Since the defective system board is sent back for repair protect the delicate processor socket springs with a socket cover Ê Place your thumb against the front edge of the protective socket cover and rest your index finger on the rear grip Make sure that the notches on the protective socket cover align with the posts on...

Page 284: ... load plate over the processor while leaving the socket lever in the open position Ê Lower the socket lever while making sure that the front edge of the load plate slides under the shoulder screw cap see close up as the lever is lowered Figure 188 Installing the protective socket cover defective system board C Ê Latch the socket lever under the load plate tab ...

Page 285: ...n Installing the UFM on page 257 TPM if applicable refer to section Installing the TPM on page 264 Ê Installing the fan module on page 152 Ê If applicable activate TPM functionality in the system BIOS under Security TPM Security Chip Setting Security Chip For more information refer to the corresponding BIOS Setup Utility reference manual Ê Reassembling on page 58 Ê Reconnect all external cables Ê ...

Page 286: ...e NIC configuration file in a Linux environment on page 88 Ê Enabling SVOM boot watchdog functionality on page 84 Ê Enabling BitLocker functionality on page 90 Ê If applicable reconfigure your network settings in the operation system according to the original configuration of the replaced controller expansion card or onboard Ê If applicable After replacing the system board on page 94 ...

Page 287: ...eliminary steps Ê Disabling BitLocker functionality on page 69 Ê Shutting down the server on page 46 Ê Disconnecting the server from the mains on page 46 Ê Remove all external cables Ê Removing the side cover on page 53 Ê Removing the front cover on page 56 I The front cover is no longer required Field Replaceable Unit FRU Hardware 20 minutes Tools Phillips PH2 No 2 screw driver Slotted screw driv...

Page 288: ... Manual TX1330 M1 Converting a tower model to a rack model 15 2 Converting a tower model to a rack model Removing the right side cover Figure 189 Removing the right side cover A Ê Remove two screws on the server rear see circles ...

Page 289: ...sengages 2 Ê Pull up on both ends of the right side cover to remove the left and right hooks from the slots on the upper chassis edge Ê Ensure that all cables and components are properly secured inside the server and that there are no loose pieces Ê Carefully turn the server upside down I At least two people are needed to turn over a fully equipped server Remove hard disk drives and power supply m...

Page 290: ...re 191 Removing rubber feet Ê Using a slotted screw driver slightly pry up on each rubber foot until it detaches Ê Bring the server back to its horizontal position I At least two people are needed to turn over a fully equipped server Remove hard disk drives and power supply units in order to facilitate the task ...

Page 291: ... 249 Ê If applicable remove all accessible drives as described in section Removing an accessible drive on page 241 Figure 192 Detaching the accessible drive cage A Ê Remove two screws from the bottom side of the server as shown Ê Bring the server back to its horizontal position I At least two people are needed to turn over a fully equipped server Remove hard disk drives and power supply units in o...

Page 292: ...ntenance Manual TX1330 M1 Converting a tower model to a rack model Figure 193 Detaching the accessible drive cage B Ê Remove two screws from the right chassis edge 1 Ê Remove two screws from the top edge of the chassis 2 ...

Page 293: ...gure 194 Removing the accessible drive cage Ê Slightly lift up the accessible drive cage to disengage its front bottom edge from the slot on the chassis floor 1 Ê Slide the accessible drive cover from under the chassis frame as shown 2 Ê Lift the accessible drive cage out of the chassis 3 ...

Page 294: ...drive cage Figure 195 Converting the accessible drive cage Ê Turn the accessible drive cover with its RACK stamping facing up 1 see close up Ê Remove the threaded bolt from the upper edge of the accessible drive cage 2 Ê Reinstall the threaded bolt on the side of the accessible drive cage as shown 3 see close up ...

Page 295: ...gure 196 Mounting the accessible drive cage Ê With its RACK stamping facing up lower the accessible drive cage into the chassis 1 Ê Slide the accessible drive cage towards the server front as far as it will go 2 Ê Ensure that the front bottom edge on the accessible drive cover properly engages in the slot in the chassis floor 3 ...

Page 296: ...ack model Figure 197 Securing the accessible drive cage A Ê Secure the accessible drive cage with two screws 1 Ê Secure the accessible drive cage with two screws 2 Ê Ensure that all cables and components are properly secured inside the server and that there are no loose pieces ...

Page 297: ... remains empty Reinstalling accessible drives Ê Reinstall the front panel rotated by 90 degrees as described in section Installing the new front panel module on page 251 Ê Reinstall all accessible drives into their original bays rotated by 90 degrees Reconnect the cables see section Cabling plans on page 303 Ê Reinstall all accessible drive filler covers and front covers as described in section In...

Page 298: ...cribed in section Installing the new intrusion switch cable on page 314 Assembling the rack front cover Figure 199 Rack mounting brackets with quick release levers I The rack front cover consists of a plastic frame and two rack mounting brackets with quick release levers Figure 200 Installing rack mounting brackets Ê Fit the rack mounting bracket on the two hooks on the rack front bezel 1 ...

Page 299: ...ers into their original locations rotated by 90 degrees Ê Ensure that an accessible drive filler cover has been installed in every empty drive bay Ê Turn the front cover face down Ê Join the two lugs on one edge of the accessible drive cover with the right inner edge of the front cover 1 Ê Fold down the accessible drive cover until it snaps in place 2 I Use the dummy covers that have been removed ...

Page 300: ...ket or http jp fujitsu com platform server primergy manual Japanese market Ê Mounting the server in the rack on page 60 Ê Reconnect all external cables Ê Connecting the server to the mains on page 67 Ê Switching on the server on page 68 Ê Update your server s chassis information on the Chassis ID EPROM integrated into the front panel board For further information on how to obtain and use the Chass...

Page 301: ...ld cables by their connectors when disconnecting them Never pull on the cable to disconnect cables Ensure that none of the cables are scraped strained or otherwise damaged while replacing system components Immediately replace cables with damaged shielding Always use shielded network cables ...

Page 302: ...ical disk drive to system board 6 HDD SAS cable T26139 Y3963 V103 from HDD backplane to SAS controller or system board 7 Hot Plug PSU power cable T26139 Y3952 V611 from power distribution board to system board 8 Power supply unit signal cable T26139 Y3956 V2 from power distribution board to system board 9 If FBU installed FBU adapter cable T26139 Y4032 V3 from FBU module to SAS controller 10 If BB...

Page 303: ...andard PSU System Board D3239 PWR1 PC2009 P30 SATA POWER FRONTPANEL USB FRONT SATA 5 MLC SATA 1 4 INTR Front Panel USB 3 0 Connectors Drive Bay 1 SATA ODD Slimline SATA ODD Drive Bay 2 USB Backup Drive Drive Bay 3 LTO 3 Backup Drive X7 X6 HDD Backplane s 1x 3 5 HDD BP 2x 2 5 HDD BP Intrusion Switch 4 P4 P9 P9 6 P1 P2 3 P5 P2 3 ...

Page 304: ...P12 P22 System Board D3239 PWR1 PC2009 P30 SATA POWER FRONTPANEL USB FRONT SATA 5 MLC SATA 1 4 INTR Front Panel USB 3 0 Connectors Drive Bay 1 SATA ODD Slimline SATA ODD Drive Bay 2 USB Backup Drive Drive Bay 3 LTO 3 Backup Drive X7 X6 HDD Backplane s 1x 3 5 HDD BP 2x 2 5 HDD BP Intrusion Switch 8 7 4 P4 P2 3 P9 P9 6 P1 P5 P2 3 ...

Page 305: ...System Board D3239 FRONTPANEL USB FRONT USB1 AUX USB1 DAT SATA 5 SATA 6 MLC SATA 1 4 INTR Front Panel USB 2 0 3 0 Connectors Drive Bay 1 SATA ODD Drive Bay 2 USB 3 0 Backup Drive Drive Bay 3 LTO 3 Backup Drive X7 X6 HDD Backplane s 1x 3 5 HDD BP 2x 2 5 HDD BP Intrusion Switch 3 5 1 2 ...

Page 306: ...oard D3239 USB1 DAT USB1 AUX Front Panel Drive Bay 1 SATA ODD Drive Bay 2 USB Backup Drive Drive Bay 3 LTO 4 5 6 Backup Drive X10 X9 X1 X1 HDD Backplanes 3 5 HDD BP 2 5 HDD BP 2 2 5 HDD BP 2 3 5 2 5 BP MLC 2 MLC 1 SAS Controller Slot 3 2 MLC 2 MLC 1 BBU FBU SAS Controller Slot 4 Boot BBU FBU 6 6 12 13 9 10 P2 P1 P3 ...

Page 307: ... PSU System Board D3239 USB1 DAT SATA POWER Front Panel Drive Bay 1 SATA ODD Drive Bay 2 USB Backup Drive Drive Bay 3 LT0 3 Backup Drive X1 X1 HDD Backplanes 2 5 HDD BP 2 3 5 2 5 BP MLC 2 MLC 1 SAS Controller Slot 3 2 MLC 2 MLC 1 BBU FBU SAS Controller Slot 4 Boot BBU FBU 6 6 12 13 9 10 P2 P1 4 P1 P2 3 ...

Page 308: ... Drive Bay 2 USB Backup Drive Drive Bay 3 SAS Backup Drive X1 X1 HDD Backplanes 3 5 HDD BP 1x 2 5 HDD BP MLC 2 MLC 1 SAS Controller Slot 3 2 6 12 13 System Board D3239 USB1 DAT USB1 AUX Drive Bay 2 USB Backup Drive Drive Bay 3 SAS Backup Drive X1 X1 HDD Backplanes 2 5 HDD BP 2 2 5 HDD BP 1 MLC 2 MLC 1 SAS Controller Slot 3 2 MLC 2 MLC 1 BBU FBU SAS Controller Slot 4 Boot BBU FBU 6 6 12 13 9 10 ...

Page 309: ...l 309 Cabling Figure 209 Riser card cabling 1 PSU Front Panel Drive Bay 1 SATA ODD Drive Bay 2 USB Backup Drive Drive Bay 3 SAS Backup Drive X9 X9 HDD Backplanes 3 5 HDD BP 2 5 HDD BP 1 System Board D3239 32 bit PCI Riser Card PCI Slot 1 11 ...

Page 310: ...tenance Manual TX1330 M1 Cabling Figure 210 Riser card cabling 2 Drive Bay 2 USB Backup Drive Drive Bay 3 SAS Backup Drive X9 X9 HDD Backplanes 3 5 HDD BP 2 5 HDD BP 1 System Board D3239 32 bit PCI Riser Card PCI Slot 1 11 ...

Page 311: ...e 46 Ê Disconnecting the server from the mains on page 46 Ê Getting access to the component on page 47 Ê Removing the rack front cover on page 52 rack server or Removing the front cover on page 56 tower server 16 3 2 Removing the defective intrusion switch cable Figure 211 Disconnecting the intrusion switch cable Field Replaceable Unit FRU Hardware 10 minutes Tools Phillips PH2 No 2 screw driver ...

Page 312: ...he HDD cage Figure 212 Removing the intrusion switch holder A Ê Remove one screw from the intrusion switch holder as shown I Replacing the intrusion switch cable is illustrated by the example of the 2 5 inch HDD model In case of the 3 5 inch HDD model the procedure is identical although the HDD bay top cover looks slightly different Figure 213 Intrusion switch holder in 3 5 inch HDD configurations...

Page 313: ...ade and Maintenance Manual 313 Cabling Figure 214 Removing the intrusion switch cable B Ê Slide back the intrusion switch holder until it disengages from the HDD bay top cover 1 Ê Remove the intrusion switch holder 2 ...

Page 314: ... Attaching a rubber bumper to the front intrusion switch I In case of rack server configurations a rubber bumper needs to be attached to the front intrusion switch as described below When working on a tower server please skip this step Ê Attach a rubber bumper C26192 Y26 C43 to the front intrusion switch as shown ...

Page 315: ...cable A Ê Place the new intrusion switch holder on the HDD bay top cover as shown 1 Ê Slide the intrusion switch holder under the front chassis rim as far as it will go 2 Figure 217 Installing the intrusion switch cable B Ê Secure the intrusion switch holder on the HDD bay top cover with one screw ...

Page 316: ...e clamps see arrows Ê Connect the intrusion switch cable to the system board connector Intrusion see circle 16 3 4 Concluding steps Ê Installing the rack front cover on page 58 rack server or Installing the front cover on page 63 tower server Ê Reassembling on page 58 Ê Connecting the server to the mains on page 67 Ê Switching on the server on page 68 ...

Page 317: ...1 Mechanical overview 17 1 1 Server front 2 5 inch HDD SSD model Figure 219 Server front 2 5 inch HDD SSD model 1 2 5 inch HDD SSD dummy module 4 ID card 2 5 25 inch dummy module 5 ODD 3 5 25 inch dummy module 6 Front panel module including front USB connectors ...

Page 318: ...nual TX1330 M1 Appendix 3 5 inch HDD model Figure 220 Server front 3 5 inch HDD model 1 3 5 inch HDD dummy module 4 ID card 2 5 25 inch dummy module 5 ODD 3 5 25 inch dummy module 6 Front panel module including front USB connectors ...

Page 319: ...ntenance Manual 319 Appendix 17 1 2 Server rear Figure 221 Server rear example standard power supply Figure 222 Server rear example redundant power supply 1 Power supply unit 3 I O panel 2 System fan 4 Optional expansion cards ...

Page 320: ...mple 2 5 inch HDD model standard power supply 1 System fan 8 SAS SATA backplane 2 Expansion card slots 9 HDD SSD drive bay 3 Processor heat sink 10 Front panel module bay 4 TPM 11 Accessible drive bay 5 CMOS battery 12 System board D3239 6 UFM 13 Memory modules 7 BBU FBU 14 Standard power supply unit ...

Page 321: ...HDD model redundant power supply 1 System fan 8 HDD drive bay 2 Expansion card slots 9 Front panel module bay 3 Processor heat sink 10 Accessible drive bay 4 TPM 11 System board D3239 5 CMOS battery 12 Power distribution board 6 UFM 13 Memory modules 7 SAS SATA backplane 14 Power supply units ...

Page 322: ...rd D3239 External connectors Slot 3 PCIe x8 MLC SATA1 4 Battery DIMM1B Indicate CSS CPU SATA6 SATA POWER PWR1 HDD ACTIVITY Intrusion TPM Slot 2 PCIe x4 Management LAN USB 9 10 Shared LAN USB 7 8 Standard LAN USB 5 6 USB Front Slot 4 PCIe x8 Slot 1 PCIe x1 Intel C224 USB1 DAT USB1AUX iRMC S4 FAN1 SYS UFM DIMM2B DIMM1A DIMM2A COM1 VGA SATA5 Intel i210 Intel i217 Jumper PC2009 P30 Frontpanel Service ...

Page 323: ...ply connector 6 USB FRONT Connector for front USB 7 FAN1 SYS Connector for system fan 8 SATA MLC1 SATA MLC connector for 3 5 inch HDD configurations 9 USB1 AUX USB 2 0 for Front panel 10 USB1 DAT USB 2 0 connector for accessible backup drive 11 INTR Intrusion switch cable connector 12 UFM Connector for USB Flash Module UFM 13 SATA 5 SATA 5 connector 14 SATA 6 SATA 6 connector 15 TPM Connector for ...

Page 324: ...EDs D the system fan module needs to be removed see section Removing the fan module on page 151 1 Indicate CSS button External connectors Slot 3 PCIe x8 MLC SATA1 4 Battery DIMM1B Indicate CSS CPU SATA6 SATA POWER PWR1 HDD ACTIVITY Intrusion TPM Slot 2 PCIe x4 Management LAN USB 9 10 Shared LAN USB 7 8 Standard LAN USB 5 6 USB Front Slot 4 PCIe x8 Slot 1 PCIe x1 Intel C224 USB1 DAT USB1AUX H iRMC ...

Page 325: ...rror B CSS Customer Self Service off no critical event CSS component yellow on prefailure detected CSS component yellow flashing CSS component failure C Identification blue on Localizes the server blue flashing Local monitor off D Memory off memory module operational orange on memory module failure E System fans off fan running orange on fan failure F PCI card off PCI card operational orange on PC...

Page 326: ...r For further information please refer to the corresponding BIOS Setup Utility reference manual The serial connector COM1 can be used as default interface or to communicate with the iRMC S4 1 Management LAN connector for iRMC S4 server management function 2 Shared LAN connector LAN1 3 Standard LAN connector LAN2 4 USB 3 0 connectors 5 USB 2 0 connectors 6 Video connector VGA 7 Serial connector COM...

Page 327: ...ic a transfer rate of 1 Gbit s green on traffic a transfer rate of 100 Mbit s off traffic a transfer rate of 10 Mbit s 3 Global error indicator off no critical event non CSS component orange on prefailure detected non CSS component orange flashing non CSS component failure CSS indicator off no critical event CSS component yellow on prefailure detected CSS component yellow flashing CSS component fa...

Page 328: ...29 PSU indicator Indicator Status Description 1 PSU operating status green on Server is switched on and functioning properly green flashing Server is switched off main voltage is present Standby mode orange on PSU failure over under voltage over temperature or fan failure orange flashing Overload warning ...

Page 329: ...n needs to be dispatched to replace the part Pos Indicator Status Description 1 HDD error indicator orange on HDD SSD SAS SATA backplane or RAID controller failure detected 2 PSU error indicator orange on Hot plug power supply unit failure detected I Only available in redundant PSU configurations 3 Temperature error indicator orange on Operating temperature levels above permitted limits 4 CPU erro...

Page 330: ... orange flashing non CSS component failure 10 HDD SSD activity indicator green flashing data access in progress 11 Power on indicator green on server is switched on and running orange on server is switched off but mains voltage is present standby mode I After connecting the server to the mains it takes about 60 secondes until the server enters the standby mode yellow orange flashing iRMC booting I...

Page 331: ...tch the server on or off I If the system is running an ACPI compliant operating system the pressing the On Off button will performs a graceful shutdown 13 NMI NMI button This button is used to troubleshoot software and device driver errors It can be pressed using the end of a paper clip V CAUTION Use this button only if directed to do so by qualified certified maintenance personnel 14 RST Reset bu...

Page 332: ...332 Upgrade and Maintenance Manual TX1330 M1 Appendix Front panel connectors Pos Description 16 USB connector blue USB 3 0 17 USB connector black USB 2 0 ...

Page 333: ...isabled RCVR Recovery BIOS enabled PWD CLR Password Clear enabled External connectors Slot 3 PCIe x8 MLC SATA1 4 Battery Indicate CSS CPU SATA6 SATA POWER PWR1 HDD ACTIVITY Intrusion TPM Slot 2 PCIe x4 Management LAN USB 9 10 Shared LAN USB 7 8 Standard LAN USB 5 6 USB Front Slot 4 PCIe x8 Slot 1 PCIe x1 Intel C224 USB1 DAT USB1AUX iRMC S4 FAN1 SYS UFM VGA SATA5 Intel i210 Intel i217 Jumper Servic...

Page 334: ...Ê Disconnecting the server from the mains on page 46 Ê Take the system down to its minimum startup configuration Ê Connecting the server to the mains on page 67 Ê Connect a keyboard mouse and display to the server Ê Switching on the server on page 68 Field Replaceable Units FRU Component Notes System board no TPM UFM or expansion cards installed CPU with CPU heat sink 1 memory module installed in ...

Page 335: ...ot included in the minimum startup configuration the server must be shut down immediately after the diagnostic process is complete POST phase has been passed The minimum startup configuration must be used exclusively for diagnostic purposes by maintenance personnel never in daily operation ...

Page 336: ...336 Upgrade and Maintenance Manual TX1330 M1 Appendix ...