4. Precautions on Wiring
1) For the main circuit wiring:
● While wiring the sizes and specifications of wires should be selected
and the wiring should be executed according to the electrical
engineering regulations to ensure the safety.
● It is better to use shielded wire or wire and conduit for power cord and
ground the shielded layer or two ends of wire conduit.
● Be sure to install a Non Fuse Breaker (NFB) between the power
supply and the input terminals (R.S.T). (If using ground fault circuit
interrupter, please choose one corresponding to high frequency)
● Never connect AC power to the output terminal (U.V.W) of the
inverter.
● Output wires mustn’t be in touch of the metal part of the inverter
enclosure, or it will result in earth short-circuit.
● Phase-shifting capacitors, LC, RC noise filters, etc, can never be
connected to the output terminals of the inverter.
● The main circuit wire must be enough far away from other control
equipments.
● When the wiring between the inverter and the motor exceeds 15
meters for 220V class or 30 meters for 380V class, much higher dV/dT
will be produced inside the coil of the motor, which will cause the
destruction to the interlay or insulation of the motor. Please use a
dedicated AC motor for the inverter or add a reactor at the inverter.
● Please lower the carrier frequency when there is a longer distance
between the inverter and the motor. Because the higher the carrier
frequency is the bigger the leakage current of high-order harmonics in
the cables will be. The leakage current will have unfavorable effect on
the inverter and other equipment.
Specifications of Non Fuse Breaker and Wire
Model
NFB(A) Input wire
mm
2
Output wire
mm
2
Control
wire
mm
2
Screw
HLPA00D423C
16
2.5
2.5
1
M4
HLPA0D7523C
16
2.5
2.5
1
M4
HLPA01D523C
32
2.5
2.5
1
M4
HLPA02D223B
32
4
4
1
M4
HLPA03D723B
40
6
6
1
M5
HLPA05D523B
63
6
6
1
M6
Summary of Contents for HLP-A Series
Page 1: ......
Page 2: ...HLP A Series...
Page 3: ......
Page 27: ...HLP A Series HLP A Series 22 1 Good 2 Good 3 Not good...
Page 69: ...HLP A Series HLP A Series 64 The following is the block diagram of multi pumps operation...
Page 106: ...HLP A Series HLP A Series 101 HLPA05D523B HLPA07D523B Unit mm HLPA05D543B HLPA07D543B Unit mm...
Page 117: ......