frequency the torque compensation will lose its f unction. When adjusting this
parameter the output current of the inverter should be increased f rom low
to high slowly according to the load of machines until it meets the starting
requirement. Do not be quick to increase it by large amplitude. Otherwise it
might cause the tripping of the inverter or the damage of the machines.
CD004 Intermediate Frequency
Set Range: 0.01-400.00 Hz Unit: 0.01 Hz Factory Setting: 2.50/3.00
Note: **
means this parameter is adjustable during operation.
This parameter is set for intermediate frequency of arbitrary V/F curve. If it is
set improperly, it will cause over-current or under-torque of the motor, or even
tripping of the inverter.
This set value of intermediate f requency is limited by the set value of base
frequency.
Code
Model
CD003 CD005 CD012 CD013 CD035
Code
Model
CD003 CD005 CD012 CD013 CD035
A00D423C 15.0
7.5
5
5
9
A001143B
19
9.5
20
20
5
A0D7523C
14.0
7
8
8
9
A001543B
19
9.5
20
20
5
A01D523C 14.0
7
10
10
8
A18D543B 18
9
25
25
5
A02D223B 13.0
6.5
10
10
8
A002243B 18
9
25
25
5
A03D723B
13.0
6.5
15
15
7
A003043B
17
8.5
30
30
4
A05D523B 12.0
6.0
15
15
6
A003743B
16
8
35
35
4
A07D523B
11.0
5.5
20
20
6
A004543B 16
8
40
40
4
A001123B
10.0
5.0
25
25
5
A005543B 15
7.5
45
45
3
A001523B 10.0
5.0
30
30
5
A007543B
15
7.5
50
50
3
A18D523B
9.0
4.5
35
35
5
A009043B
14
7
75
75
2
A002223B
9.0
4.5
50
50
4
A011043B
14
7
100
100
2
A003023B
8.0
4.0
70
70
4
A013243B
13
6.5
150
150
2
A003723B
7.0
3.5
80
80
4
A016043B 13
6.5
150
150
2
A004523B
6.0
3.0
100
100
3
A018543B
12
6
200
200
2
A005523B
5.0
2.5
120
120
3
A020043B 12
6
200
200
2
CD005 Min.Voltage
Set Range: 0.1V* Unit: 0.1V Factory Setting:*
This parameter is set for minimum starting voltage of V/F curve.
This set value of minimum voltage is limited by the voltage at the maximum
frequency.
CD006 Min.Frequeny
Setting Range: 0.01~20.00Hz Unit: 0.01Hz Factory Setting:0.50
This parameter is set for minimum starting frequency of V/F curve.
The following chart is about V/F curve
、
Acceleration-Deceleration Time
and Factory Setting of Carrier of A series.
Summary of Contents for HLP-A Series
Page 1: ......
Page 2: ...HLP A Series...
Page 3: ......
Page 27: ...HLP A Series HLP A Series 22 1 Good 2 Good 3 Not good...
Page 69: ...HLP A Series HLP A Series 64 The following is the block diagram of multi pumps operation...
Page 106: ...HLP A Series HLP A Series 101 HLPA05D523B HLPA07D523B Unit mm HLPA05D543B HLPA07D543B Unit mm...
Page 117: ......