HLP-A Series
HLP-A Series
-
33
-
Parameter and Function List (Part 6)
Category
Code
Function
Set Range & Function
Explanation
Factory
Setting
Pa
ram
ete
rs o
f M
otor
Fu
nc
tio
ns
CD130 Rated Motor Voltage Set according to Motor
nameplate
*
CD131 Rated Motor Current Set according to Motor
nameplate
*
CD132 Motor pole number.
02—60
04
CD133 Rated Motor
Revolution
00-9999r/min
1440
CD134 Motor no-load current 0~100%
40
CD135 Motor slip
compensation
0—1000
0
CD136
~
CD139
Reserved
Pa
ram
ete
rs o
f S
pe
cia
l F
un
ctio
ns
CD140 DC Braking level
0.0~20.0%
2.0
CD141 DC Braking time at
start
0.0~25.0S
0.0
CD142 DC Braking time at
stop
0.0~25.0S
0.0
CD143
Frequency track time
0.0~20.0S
5.0
CD144 Current level for
frequency track
0~200%
150
CD145 Restart after
instantaneous Stop
0: Invalid 1: Frequency track
0
CD146 Allowable Power-
Breakdown Time
0.1~5.0S
0.5
CD147
Number of Abnormal
Restart
0—10
00
CD148 Auto Voltage
Regulation
0: Invalid 1: Valid
1
CD149
Auto Energy Saving 0.0~20.0%
0.0
CD150 Proportional Constant
(P)
0.0~1000.0%
100.0
CD151 Integral Time (I)
0.1~*
5.0
CD152 Differential Time (D) 0.00~10.00S
0.00
CD153 Target value
0.0~100.0%
*
CD154 Target value select
0: set by the operator 1:set by
external terminals (0-10V)
0
CD155 PID upper limit
0~100%
100
CD156 PID lower limit
0~100%
0
CD157
~
CD159
Reserved
CD160 Communication
Addresses
0-250
0
Summary of Contents for HLP-A Series
Page 1: ......
Page 2: ...HLP A Series...
Page 3: ......
Page 27: ...HLP A Series HLP A Series 22 1 Good 2 Good 3 Not good...
Page 69: ...HLP A Series HLP A Series 64 The following is the block diagram of multi pumps operation...
Page 106: ...HLP A Series HLP A Series 101 HLPA05D523B HLPA07D523B Unit mm HLPA05D543B HLPA07D543B Unit mm...
Page 117: ......