HLP-A Series
HLP-A Series
-
46
-
of the inverter will be increased or decreased by one unit.
When the switch of the terminal is hold the frequency will
increase or decrease rapidly to a point and then increase or
decrease
26: Down Function at even speed. When the power is up again after the power
breakdown the changed frequency will not be memorized.
27: Counter Pulse When this terminal is set for the counter it can receive the
pulse signal of ≤250HZ and counts.
28: Counter Reset When this contact acts it will clear the present counting
values displayed, restore C00 and restart counting.
29: Drawing Start When this contact is triggered the drawing action starts.
30:AutoPLC Start This contact can be used to achieve the function of
AutoPLC start.
31: AutoPLC Reset Suspend This contact can be used to achieve the f unction
of AutoPLC clear suspend.
32: PID Valid
When this contact is closed, PID f unction starts. PID
Function start is only valid during operation.
Explanation:
1. Three multi-function terminals can be used for the connection method of
three-wire system for the realization of switching of FOR/REV rotation,
which is extensively applied in the cases of FOR/REV switching of
photoelectric switches.
①
Select FOR, REV and RST.
②
Parameter setting:
CD033=1 for external control CD050=02 for FOR rotation
CD051=03 for REV Rotation CD052=04 for Stop
③
Action Description:
When triggering FOR, the inverter will rotate forward
(start);
When triggering REV, the inverter will rotate reverse;
When pressing STOP, the inverter will stop.
①
Select FOR,REV
②
Parameter Setting:
CD033=1 for external control CD050=01 for Run function
CD051=05 for F/R function
While K2 is off, the inverter will rotate forward.
While K2 is on, the inverter will rotate reverse.
2. RUN, DCM, F/R can be used for Start, Stop and switching of FOR/REV:
Summary of Contents for HLP-A Series
Page 1: ......
Page 2: ...HLP A Series...
Page 3: ......
Page 27: ...HLP A Series HLP A Series 22 1 Good 2 Good 3 Not good...
Page 69: ...HLP A Series HLP A Series 64 The following is the block diagram of multi pumps operation...
Page 106: ...HLP A Series HLP A Series 101 HLPA05D523B HLPA07D523B Unit mm HLPA05D543B HLPA07D543B Unit mm...
Page 117: ......