HLP-A Series
HLP-A Series
-
47
-
3. Description of Ramp Time 1 and 2:
1) This f unction is only valid when CD076 is set to 0, 1 and 2. Under the
disturbance and internal control multi-speed it is invalid.
2) Any two multi-inputs can be combined for 4 kinds of ramp time for
selection.
3) The related multi-inputs are set for Ramp Time 1, 2. Take the terminals of
SPH and SPM as example, when SPH CD053 is set to 23 and SPM CD054 is
set to 24, SPH and SPM are now Ramp Time 1, 2.
SPH
SPM
Result
OFF
OFF
Ramp Time 1
ON
OFF
Ramp Time 2
OFF
ON
Ramp Time 3
ON
ON
Ramp Time 4
4. Function description of High, Middle and low speed terminals:
RUN
SPL
SPM
SPH
Result
ON
OFF
OFF
OFF
Main speed, the frequency runs at the set
value of CD000.
ON
ON
OFF
OFF
Low speed, the frequency runs at the set
value of CD080.
ON ON/OFF
ON
OFF
Middle speed, the frequency runs at the set
value of CD081.
ON ON/OFF ON/OFF ON
High speed, the frequency runs at the set
value of CD082.